SiAF332111E Field Settings for Outdoor Unit (10/12 HP Models)
Part 5 Field Settings and Test Operation 153
Accessing modes
BS1 is used to change the mode you want to access.
Access mode 1
Press BS1 once. Segment indication changes to:
Access mode 2
Press BS1 for at least 5 seconds. Segment indication changes to:
Mode 1
Mode 1 is used to set basic settings and to monitor the status of the unit.
Changing and access the setting in mode 1:
To quit and return to the initial status, press BS1.
Example:
[A-B]: C in this case defined as: A = 1; B = 10; C = the value we want to know/monitor:
Make sure the segment indication is as during normal operation (default situation when
shipped from factory).
Press BS1 once; result segment display:
Result: mode 1 is accessed.
Press BS2 10 times; result segment display:
Result: mode 1 setting 10 is addressed.
Press BS3 1 time; the value which is returned (depending on the actual field situation), is the
amount of indoor units which are connected to the system.
Result: mode 1 setting 10 is addressed and selected, return value is monitored information.
To leave the monitoring function, press BS1 once, you will return to the default situation
when shipped from factory.
INFORMATION: If you get confused in the middle of the process, press BS1.
Then it returns to idle situation (no indication on segment displays: blank)
Once mode 1 is selected (press BS1 once), you can select the wanted setting. It is
done by pushing BS2. Accessing the selected setting's value is done by pressing
BS3 once.
Checking the content of parameter [1-10] (to know how many indoor units are
connected to the system).