SiAF332111E Field Settings for Outdoor Unit (10/12 HP Models)
Part 5 Field Settings and Test Operation 159
[2-30]: Power consumption limitation level (step 1) via the external control adaptor
(DTA104A61/62)
If the system needs to be running under power consumption limitation conditions
when an external signal is sent to the unit, this setting defines the level power
consumption limitation that will be applied for step 1. The level is according to the
table.
Value
[2-30]
Power consumption limitation
1 60%
2 65%
3
70% (default)
4 75%
5 80%
6 85%
7 90%
8 95%
[2-31]: Power consumption limitation level (step 2) via the external control adaptor
(DTA104A61/62)
If the system needs to be running under power consumption limitation conditions
when an external signal is sent to the unit, this setting defines the level power
consumption limitation that will be applied for step 2. The level is according to the
table.
Value
[2-31]
Power consumption limitation
1
40% (default)
2 50%
3 55%
[2-32]: Forced, all time, power consumption limitation operation (no external control adaptor
is required to perform power consumption limitation)
If the system always needs to be running under power consumption limitation
conditions, this setting activates and defines the level power consumption limitation
that will be applied continuously. The level is according to the table.
Value
[2-32]
Restriction reference
0
Function not active (default)
1 Follows [2-30] setting
2 Follows [2-31] setting
[2-35]: Height difference setting
Default value: 1
In case the outdoor unit is installed in the lowest position (indoor units are installed
on a higher position than outdoor units) and the height difference between the
highest indoor unit and the outdoor unit exceeds 40 m (131 ft), the setting [2-35]
should be changed to 0.
[2-45]: Technical cooling
Value
[2-45]
Description
0
No technical cooling available (default)
1 Technical cooling available