Loading...
Troubleshooting by Error Code SiAF332111E
244 Part 6 Service Diagnosis
Troubleshooting
There is
foreign matter around the
applicable fan.
Remove the foreign matter.
YES
Check for the connections of fan motor connector.
NO
Turn OFF the power supply, and then wait for a period of 10 minutes.
Connector is
disconnected.
Insert the connector.
YES
NO
NO
Replace the relevant PCB (2).
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A
Check for Connection of Connector
The fan
can be rotated
by hand when
disconnecting the
connector from the
fan motor.
Replace the fan motor (M1F).
NO
Resistance
between the fan
motor power supply cable
terminal and the motor frame
(metallic part) is less
than 1 M.
Replace the fan motor (M1F).
YES
YES
NO
The fuse
(1)
on the
relevant PCB
(2)
has
continuity.