Troubleshooting by Error Code SiAF332111E
334 Part 6 Service Diagnosis
Troubleshooting
YES
NO
NO
NO
YES
NO
YES
NO
YES
YES
NO
YES
Concurrently reset the
power supply of all the
centralized controllers.
Connect the power
supply of the
centralized controller.
Set the reset switch to
the normal position.
Correct the wiring.
Refer to the troubleshooting
of the centralized controllers
or the schedule timers.
Go to the next page.
A
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are any
connected centralized
controllers removed or the
address changed?
Are the
reset switches of
all the centralized controllers
set to the normal
position?
Does the
power supply of all the
centralized controllers
connect?
Is the
connection wiring broken
or wrong?
Does
the centralized
controller or the schedule
timer connect?
Is any
error displayed on
the centralized controller or
the schedule
timer?