SiAF332111E Outline of Control (Indoor Unit)
Part 4 Functions and Control 89
3.11.2 Operational Concept (Standard Panel)
Cooling
: Factory setting
3.11.3 Operational Concept (Designer Panel)
Cooling
: Factory setting
Movement pattern (a) (b) (c) (d)
Appearance
Time (seconds)
13 (23)-14
01: Pattern 1
120 600 120 600
02: Pattern 2 120 600 0 0
03: Pattern 3 0 0 120 600
04: Pattern 4 120 600 120 600
Indicates the horizontal flap is in the position of reducing airflow volume (the flap is inverted).
Movement pattern (a) (b) (c) (d)
Appearance
Time
(seconds)
13 (23)-14
01: Pattern 1
120 600 120 600
02: Pattern 2 120 600 0 0
03: Pattern 3 0 0 120 600
04: Pattern 4 120 600 120 600
Indicates the horizontal flap is in the position of reducing airflow volume (the flap is inverted).