Danfoss ECL COMFORT - ECL Card Settings (Circuit II); Time and Date

Danfoss ECL COMFORT
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control & overviews
ECL Card settings
(circuit II)
30b
A Time and date Section 17
B System information Sections 18 & 19
C Storage tank sensor(s)
Section 20
Setting ranges Factory settings Your settings
1
Cut-out temperature difference
1 ... 99 K 15 K
See section 27
2
Cut-in temperature difference
1 ... 99 K 20 K
See section 27
3
4
Proportional band, Xp
1 ... 250 K 80 K
See section 26
5
Integration time constant, Tn
5 ... 999 sec. 30 sec.
See section 26
6
Running time of the motorized control
valve
5 ... 250 sec. 35 sec.
See section 26
7
Neutral zone, Nz
0 ... 9 K 3 K
See section 26