Danfoss ECL COMFORT - Pump Exercise; Valve Exercise; Gear Motor; Thermo Actuator

Danfoss ECL COMFORT
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The grey
side of the
ECL Card
Extended service
32f
Service parameter(s) 22-24
23 Valve exercise
Circuit Setting range Factory setting
I / (II) ON / OFF OFF / (OFF)
Exercises the valve to avoid blocking in periods without heat
demand.
ON: The valve receives a signal to open and close
every third day around noon.
OFF: The valve exercise is not active.
22 Pump exercise
Circuit Setting range Factory setting
I / (II) ON / OFF ON / (ON)
Exercises the pump to avoid blocking in periods without heat
demand.
ON: The pump is switched ON for 1 minute every
third day around noon.
OFF: The pump exercise is not active.
24 Gear motor / thermo actuator
Circuit Setting range Factory setting
(I) / (II) ON / OFF (ON) / (ON)
Choose the actuator type for your valve.
ON: Gear motor
OFF: Thermo actuator (ABV type)
Control parameters (lines 4-7) are overruled if thermo actuator is
chosen (OFF).