The grey
side of the
ECL Card
Extended service
32f
Service parameter(s) 22-24
23  Valve exercise
Circuit Setting range Factory setting
I / (II) ON / OFF OFF / (OFF)
Exercises the valve to avoid blocking in periods without heat 
demand.
ON:   The valve receives a signal to open and close 
every third day around noon.
OFF:   The valve exercise is not active.
22  Pump exercise
Circuit Setting range Factory setting
I / (II) ON / OFF ON / (ON)
Exercises the pump to avoid blocking in periods without heat 
demand.
ON:   The pump is switched ON for 1 minute every 
third day around noon.
OFF:   The pump exercise is not active.
24  Gear motor / thermo actuator
Circuit Setting range Factory setting
(I) / (II) ON / OFF (ON) / (ON)
Choose the actuator type for your valve.
ON:   Gear motor
OFF:   Thermo actuator (ABV type)
Control parameters (lines 4-7) are overruled if thermo actuator is 
chosen (OFF).