VI.7C.Q2.02
Card C47
2005.09
Sketch your application
The ECL Comfort controller series is designed for a wide 
range of heating, hot-water and cooling systems with 
different configurations and capacities.
If your system differs from the diagrams shown in section 
10, you may want to make a sketch of the system about to 
be installed. This makes it easier to use the Installer’s Guide, 
which will guide you step-by-step from installation to final 
adjustments before the end-user takes over. 
The controller is pre-programmed with factory settings that are 
shown in the relevant sections of this guide. 
However, you might come across some settings that are not listed 
in this instruction. These settings could be related either to recent 
updates or the use of optional modules (which are described in 
the instructions in question).
How to use this guide
This guide is divided into two parts:
•   User’s Guide:  Yellow sections 1-7
•   Installer's Guide:  Grey sections 10 and onwards
The application C47 is very flexible. These are the basic 
principles:
Heating: 
Typically, the flow temperature is always adjusted according to 
your requirements.
The flow temperature sensor (S2) is the most important sensor. 
The desired flow temperature at S2 is calculated in the ECL 
controller, based on the outdoor temperature (S1). The lower the 
outdoor temperature, the higher the desired flow temperature.
The motorized control valve (M1) is opened gradually when the 
flow temperature is lower than the desired flow temperature and 
vice versa.   
The return temperature (S3) to the district heating supply should 
not be too high. If so, the desired flow temperature can be 
adjusted (typically to a lower value) thus resulting in a gradual 
closing of the motorized control valve. 
If the measured room temperature does not equal the desired 
room temperature, the desired flow temperature can be adjusted.
DHW: 
If the measured DHW temperature is lower than the desired DHW 
heating temperature minus the cut-in difference, the desired flow 
temperature at S4 is kept in order to heat the DHW.
Before you start