Extended service
32q
Service parameter(s) 85
85  Assignment (number) of heat meters
Circuit Setting range Factory setting
II ON / OFF OFF
If the flow or heating supply has to be limited, the number of heat 
meters and their position must be determined.
ON:    Two heat meters are used. This setting only 
applies to heating system types 2, 2a, 3, 6, 
and 6a with primarily connected DHW. The 
heating supply or flow in circuit I (heating 
circuit) is limited based on a signal from 
heat meter 1. The same function applies to 
circuit II (DHW) and heat meter 2.
OFF:   One heat meter is used. This setting 
especially applies to heating system types 
with secondarily connected DHW, e.g. 
heating system types 1, 4 und 5. However, 
one heat meter can also be used for 
heating system types 2, 2a, 3, 6, and 6a. For 
these types the max. heating supply or the 
max. flow is limited in parallel operation 
from the heating or DHW circuit.
This function is only active when an M-Bus or the pulse module 
ECA 84 / ECA 88 is connected. Other relevant settings are 
described in the related instructions.