EasyManuals Logo

Danfoss ECL COMFORT User Manual

Danfoss ECL COMFORT
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
The grey
side of the
ECL Card
Extended service
Service parameter(s) 20-21
32e
20 Optimization based on room / outdoor temperature
Circuit
Setting range Factory setting
(I) / (II)
ON / OFF (OFF) / (OFF)
The optimized start and stop time can be based on either room or
outdoor temperature.
ON: Optimization based on room temperature, if
measured.
OFF: Optimization based on outdoor
temperature. Use this setting if the room
temperature is not measured.
21 Total stop
Circuit Setting range Factory setting
I / (II) ON / OFF OFF / (OFF)
Decide whether you want a total stop during the setback
temperature period.
ON: The desired flow temperature is lowered
to 10 °C. The min. setting of the flow
temperature (line 2, section 22) is overruled.
Desired flow
temp. (°C)
10 °C
Time
OFF: No total stop
Desired flow
temp. (°C)
10 °C
Time

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL COMFORT and is the answer not in the manual?

Danfoss ECL COMFORT Specifications

General IconGeneral
TypeElectronic controller
DisplayLCD with backlight
Protection ClassIP 41
CommunicationModbus
MountingWall mount
ApplicationHeating, cooling
Relative Humidity10% to 90% (non-condensing)
Display FeaturesGraphical

Related product manuals