Frequency converter PK75 P1K5 P2K2 P3K0 P4KO P5K5 P7K5 P11K P15K P18K
Typical shaft output [kW] 0.75 1.5 2.2 3.0 4.0 5.5 7.5 11 15 18.5
Typical shaft output [hp] 1.0 2.0 3.0 4.0 5.0 7.5 10.0 15 20 25
IP54 frame I2 I2 I2 I2 I2 I3 I3 I4 I4 I4
Max. cable size in terminals (mains, motor)
[mm
2
/AWG]
4/10 4/10 4/10 4/10 4/10 4/10 4/10 16/6 16/6 16/6
Output current
40 °C ambient temperature
Continuous (3x380-440 V) [A] 2.2 3.7 5.3 7.2 9.0 12.0 15.5 23.0 31.0 37.0
Intermittent (3x380-440 V) [A] 2.4 4.1 5.8 7.9 9.9 13.2 17.1 25.3 34.0 40.7
Continuous (3x440-480 V) [A] 2.1 3.4 4.8 6.3 8.2 11.0 14.0 21.0 27.0 34.0
Intermittent (3x440-480 V) [A] 2.3 3.7 5.3 6.9 9.0 12.1 15.4 23.1 29.7 37.4
Max. input current
Continuous (3x380-440 V )[A] 2.1 3.5 4.7 6.3 8.3 11.2 15.1 22.1 29.9 35.2
Intermittent (3x380-440 V) [A] 2.3 3.9 5.2 6.9 9.1 12.3 16.6 24.3 32.9 38.7
Continuous (3x440-480 V) [A] 1.8 2.9 3.9 5.3 6.8 9.4 12.6 18.4 24.7 29.3
Intermittent (3 x 440-480 V) [A] 2.0 3.2 4.3 5.8 7.5 10.3 13.9 20.2 27.2 32.2
Max. mains fuses
See 5.2.3 Fuses and Circuit Breakers
Estimated power loss [W], best case/typical
1)
21/
16
46/
57
46/
58
66/
83
95/
118
104/
131
159/
198
248/
274
353/
379
412/
456
Weight enclosure IP54 [kg] 5.3 5.3 5.3 5.3 5.3 7.2 7.2 13.8 13.8 13.8
Efficiency [%], best case/typical
1)
98.0/
97.6
97.7/
97.2
98.3/
97.9
98.2/
97.8
98.0/
97.6
98.4/
98.0
98.2/
97.8
98.1/
97.9
98.0/
97.8
98.1/
97.9
Output current - 50 °C ambient temperature
Continuous (3x380-440 V) [A] 1.93 3.7 4.85 6.3 7.5 10.9 14.0 20.9 28.0 33.0
Intermittent (3x380-440 V) [A] 2.1 4.07 5.4 6.9 9.2 12.0 15.4 23.0 30.8 36.3
Continuous (3x440-480 V) [A] 1.8 3.4 4.4 5.5 6.8 10.0 12.6 19.1 24.0 30.0
Intermittent (3x440-480 V) [A] 2.0 3.7 4.8 6.1 8.3 11.0 13.9 21.0 26.4 33.0
Table 8.4 3x380-480 V AC, PK75-P18K, I2-I4
1) At rated load conditions