Frequency converter P22K P30K P37K P45K P55K P75K P90K
Typical shaft output [kW] 22.0 30.0 37.0 45.0 55.0 75.0 90.0
Typical shaft output [hp] 30.0 40.0 50.0 60.0 70.0 100.0 125.0
IP54 frame I6 I6 I6 I7 I7 I8 I8
Max. cable size in terminals (mains, motor) [mm
2
/AWG]
35/2 35/2 35/2 50/1 50/1 95/(3/0) 120/(4/0)
Output current
40 °C ambient temperature
Continuous (3x380-440 V) [A] 44.0 61.0 73.0 90.0 106.0 147.0 177.0
Intermittent (3x380-440 V) [A] 48.4 67.1 80.3 99.0 116.6 161.7 194.7
Continuous (3x440-480 V) [A] 40.0 52.0 65.0 80.0 105.0 130.0 160.0
Intermittent (3x440-480 V) [A] 44.0 57.2 71.5 88.0 115.5 143.0 176.0
Max. input current
Continuous (3x380-440 V )[A] 41.8 57.0 70.3 84.2 102.9 140.3 165.6
Intermittent (3x380-440 V) [A] 46.0 62.7 77.4 92.6 113.1 154.3 182.2
Continuous (3x440-480 V) [A] 36.0 49.2 60.6 72.5 88.6 120.9 142.7
Intermittent (3 x 440-480 V) [A] 39.6 54.1 66.7 79.8 97.5 132.9 157.0
Max. mains fuses
Estimated power loss [W], best case/typical
1)
496 734 995 840 1099 1520 1781
Weight enclosure IP54 [kg] 27 27 27 45 45 65 65
Efficiency [%], best case/Typical
1)
98.0 97.8 97.6 98.3 98.2 98.1 98.3
Output current - 50 °C ambient temperature
Continuous (3x380-440 V) [A] 35.2 48.8 58.4 63.0 74.2 102.9 123.9
Intermittent (3x380-440 V) [A] 38.7 53.9 64.2 69.3 81.6 113.2 136.3
Continuous (3x440-480 V) [A] 32.0 41.6 52.0 56.0 73.5 91.0 112.0
Intermittent (3x440-480 V) [A] 35.2 45.8 57.2 61.6 80.9 100.1 123.2
Table 8.5 3x380-480 V AC, P11K-P90K, I6-I8
1) At rated load conditions