Parameter 14-22 Operation Mode does not reset settings
such as the following:
•
Running hours
•
Serial communication options
•
Personal menu settings
•
Fault log, alarm log, and other monitoring
functions
Recommended initialization
1. Press [Main Menu] twice to access parameters.
2. Go to parameter 14-22 Operation Mode and
press [OK].
3. Scroll to Initialization and press [OK].
4. Remove power to the unit and wait for the
display to turn o.
5. Apply power to the unit. Default parameter
settings are restored during start-up. Start-up
takes slightly longer than normal.
6. After alarm 80, Drive initialized to default value
appears, press [Reset].
Manual initialization
Manual initialization resets all factory settings except for
the following:
•
Parameter 15-00 Operating hours
•
Parameter 15-03 Power Up's
•
Parameter 15-04 Over Temp's
•
Parameter 15-05 Over Volt's
To perform manual initialization:
1. Remove power to the unit and wait for the
display to turn o.
2. Press and hold [Status], [Main Menu], and [OK]
simultaneously while applying power to the unit
(approximately 5 s or until an audible click
sounds and the fan starts). Start-up takes slightly
longer than normal.
Commissioning VLT® HVAC Drive FC 102
54 Danfoss A/S © 01/2017 All rights reserved. MG16O102