3 Product Overview
3.1 Intended Use
The drive is an electronic motor controller that converts AC mains input into a variable AC waveform output. The frequency
and voltage of the output are regulated to control the motor speed or torque. The drive is designed to:
Regulate motor speed in response to system feedback or to remote commands from external controllers.
Monitor system and motor status.
Provide motor overload protection.
The drive is allowed for use in industrial and commercial environments in accordance with local laws and standards.
Depending on conguration, the drive can be used in standalone applications or form part of a larger system or installation.
NOTICE
In a residential environment, this product can cause radio interference, in which case supplementary mitigation
measures can be required.
Foreseeable misuse
Do not use the drive in applications which are non-compliant with specied operating conditions and environments. Ensure
compliance with the conditions specied in chapter 9 Specications.
3.2 Power Ratings, Weights, and Dimensions
Table 3.1 provides dimensions for standard congurations. For dimensions on optional congurations, see chapter 9 Speci-
cations.
Enclosure size E1h E2h E3h E4h
Rated power at 380–480 V [kW (hp)] 355–450
(500–600)
500–560
(650–750)
355–450
(500–600)
500–560
(650–750)
Rated power at 525–690 V [kW (hp)] 450–630
(450–650)
710–800
(750–950)
450–630
(450–650)
710–800
(750–950)
Enclosure protection rating IP21/Type 1
IP54/Type 12
IP21/Type 1
IP54/Type 12
IP20/
Chassis
IP 20/
Chassis
Unit dimensions
Height [mm (in)] 2043 (80.4) 2043 (80.4) 1578 (62.1) 1578 (62.1)
Width [mm (in)] 602 (23.7) 698 (27.5) 506 (19.9) 604 (23.89)
Depth [mm (in)] 513 (20.2) 513 (20.2) 482 (19.0) 482 (19.0)
Weight [kg (lb)] 295 (650) 318 (700) 272 (600) 295 (650)
Shipping dimensions
Height [mm (in)] 768 (30.2) 768 (30.2) 746 (29.4) 746 (29.4)
Width [mm (in)] 2191 (86.3) 2191 (86.3) 1759 (69.3) 1759 (69.3)
Depth [mm (in)] 870 (34.3) 870 (34.3) 794 (31.3) 794 (31.3)
Weight [kg (lb)]
Table 3.1 Enclosure Power Ratings and Dimensions
Product Overview VLT® HVAC Drive FC 102
6 Danfoss A/S © 01/2017 All rights reserved. MG16O102
33

Table of Contents

Other manuals for Danfoss FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 102 and is the answer not in the manual?

Danfoss FC 102 Specifications

General IconGeneral
BrandDanfoss
ModelFC 102
CategoryDC Drives
LanguageEnglish

Related product manuals