Danfoss vlt aqua - Analog inputs:

Danfoss vlt aqua
298 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[104] Torque rel to lim
[105] Torque rel to rated
[106] Power
[107] Speed
[108] Torque
[113] Ext. closed loop 1
[114] Ext. closed loop 2
[115] Ext. closed loop 3
[116] PID Reference
[130] Output freq. 4-20mA
[131] Reference 4-20mA
[132] Feedback 4-20mA
[133] Motor cur. 4-20mA
[134] Torque % lim.
4-20mA
[135] Torque % nom
4-20mA
[136] Power 4-20mA
[137] Speed 4-20mA
[138] Torque 4-20mA
[139] Bus ctrl. 0-20 mA
[140] Bus ctrl. 4-20 mA
[141] Bus ctrl. 0-20 mA,
timeout
[142] Bus ctrl. 4-20 mA,
timeout
[143] Ext. Closed Loop 1,
4-20 mA
[144] Ext. Closed Loop 2,
4-20 mA
[145] Ext. Closed Loop 3,
4-20 mA
6-51 Terminal 42 Output Min Scale
Range: Function:
0%
*
[0 – 200%] Scale the minimum output of the selected analog signal at ter-
minal 42, as a percentage of the maximum signal value. E.g. if
0 mA (or 0 Hz) is desired at 25% of the maximum output value,
then programme 25%. Scaling values up to 100% can never be
higher than the corresponding setting in par. 6-52.
VLT
®
AQUA Drive Programming Guide 2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
103