[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
Default refers to the FC Protocol
8-33 Parity/Stop Bits
Option: Function:
Parity and Stop Bits for the protocol (par. 8-30,
Protocol
) using
the FC Port. For some of the protocols, not all options will be
visible. Default depends on the protocol selected.
[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range: Function:
10 ms
*
[5 - 500 ms] Specify the minimum delay time between receiving a request
and transmitting a response. This is used for overcoming mo-
dem turnaround delays.
8-36 Max Response Delay
Range: Function:
5000
ms
*
[5 - 10000 ms] Specify the maximum permissible delay time between transmit-
ting a request and receiving a response. Exceeding this delay
time will cause control word time-out.
8-37 Max Inter-Char Delay
Range: Function:
25 ms
*
[0 - 35 ms] Specify the maximum permissible time interval between receipt
of two bytes. This parameter activates time-out if transmission
is interrupted.
This parameter is active only when par. 8-30 is set to
FC MC
[1]
protocol.
2.9.5. Telegram Selection, 8-40
8-40 Telegram Selection
Option: Function:
Enables use of freely configurable telegrams or standard tele-
grams for the FC port.
[1]
*
Standard telegram 1
[101] PPO 1
[102] PPO 2
[103] PPO 3
VLT
®
AQUA Drive Programming Guide 2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
111