EasyManuals Logo

Danfoss vlt aqua Programming Guide

Danfoss vlt aqua
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #87 background imageLoading...
Page #87 background image
[169] Drive in auto mode Output is high when the frequency converter is in Hand on mode
(as indicated by the LED light above [Auto on].
[180] Clock Fault The clock function has been reset to default (2000-01-01) be-
cause of a power failure.
[181] Preventive Mainte-
nance
One or more of the Preventive Maintenance Events programmed
in par. 23-10, Preventive Maintenance Item, has passed the
time for the specified action in par. 23-11, Maintenance Action.
[190] No-Flow A No-Flow situation or Minimum Speed situation has been de-
tected if enabled in
Minimum Speed Detection
. par. 22-21 and/
or
No-Flow Detection
, par. 22-22.
[191] Dry Pump A Dry Pump condition has been detected. This function must be
enabled in par. 22-26, Dry Pump Function.
[192] End of Curve Active when an End of Curve condition is present.
[193] Sleep Mode The frequency converter/system has turned into sleep mode.
See
Sleep mode
, par. 22-4*.
[194] Broken Belt A Broken Belt condition has been detected. This function must
be enabled in par. 22-60, Broken Belt Detection.
[195] Bypass Valve Control The bypass valve control (Digital / Relay output in the frequency
converter) is used for compressor systems to unload the com-
pressor during start-up by using a bypass valve. After the start
command is given the bypass valve will be open until the fre-
quency converter reaches
Motor speed low limit
, par. 4 -11) .
After the limit has been reached the bypass valve will be closed,
allowing the compressor to operate normally. This procedure
will not be activated again before a new start is initiated and the
frequency converter speed is zero during the receiving of start
signal.
Start Delay
, par. 1-71 can be used in order to delay the
motor start. The Bypass valve control principle:
The below setting options are all related to the Cascade Controller.
Wiring diagrams and settings for parameter, see group 25-** for more details.
[196] Pipe Filling Active when the Pipe Fill function is operating. See par. 29-0*.
[200] Full Capacity All pumps running and at full speed
VLT
®
AQUA Drive Programming Guide 2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
87
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals