Parameter 23-12 Maintenance Base
Table 1030: Parameter 23-12 Maintenance Base
Default value: Size related
Parameter type: Option, Array [6]
Change during operation: True
Select the time base to be associated with the preventive maintenance event.
Disables the preventive maintenance event.
The number of hours the motor has run. Running hours are not reset at power-on. Specify the main-
tenance time interval in parameter 23-13 Maintenance Interval.
The number of hours the drive has run. Operating hours are not reset at power-on. Specify the
maintenance time interval in parameter 23-13 Maintenance Interval.
Uses the internal clock. Specify the date and time of the next maintenance occurrence in parameter
23-14 Maintenance Date and Time.
Parameter 23-13 Maintenance Interval
Table 1031: Parameter 23-13 Maintenance Interval
23-13 Maintenance Interval
Parameter type: Range, 1 - 2147483647, Array [6]
Change during operation: True
Set the interval associated with the current preventive maintenance event. This parameter is only used if [1] Running Hours or [2]
Operating Hours is selected in parameter 23-12 Maintenance Base. The timer is reset in parameter 23-15 Reset Maintenance Word.
Example
A preventive maintenance event is set up Monday at 8:00. Parameter 23-12 Maintenance Base is [2] Operating hours and parameter
23-13 Maintenance Interval is 7 x 24 hours=168 hours. Next maintenance event is indicated the following Monday at 8:00. If this
maintenance event is not reset until Tuesday at 9:00, the next occurrence is the following Tuesday at 9:00.
Parameter 23-14 Maintenance Data and Time
Table 1032: Parameter 23-14 Maintenance Data and Time
23-14 Maintenance Data and Time
Default value: Size related
Parameter type: Range, 0 - 0, Array [6]
Change during operation: True
Set the date and time for the next maintenance occurrence if the preventive maintenance event is based on date/time. Date format
depends on the setting in parameter 0-71 Date Format while the time format depends on the setting in parameter 0-72 Time Format.
AU275636650261en-000101 / 130R0334560 | Danfoss A/S © 2022.12
Parameter Descriptions