N O T I C E
The drive has no back-up of the clock function. The set date/time is reset to default (2000-01-01 00:00) after a power-down. In
parameter 0-79 Clock Fault, it is possible to program a warning if the clock has not been set properly, for example after a power-
down. Set the time at least 1 hour later than actual time.
N O T I C E
When mounting a VLT® Analog I/O option MCB 109 option card, a battery back-up of the date and time is included.
Parameter 23-15 Reset Maintenance Word
Table 1033: Parameter 23-15 Reset Maintenance Word
23-15 Reset Maintenance Word
Default value: [0] Do not reset
Change during operation: True
N O T I C E
When messages are reset, maintenance item, action, and maintenance date/time are not canceled. Parameter 23-12 Maintenance
Time Base is set to [0] Disabled.
Set this parameter to [1] Do reset to reset the maintenance word in parameter 16-96 Maintenance Word and reset the message shown
in the LCP. This parameter changes back to [0] Do not reset when pressing [OK].
Parameter 23-16 Maintenance Text
Table 1034: Parameter 23-16 Maintenance Text
Parameter type: Range, 0 - 20, Array [6]
Change during operation: True
6 individual texts (Maintenance Text 0...Maintenance Text 5) can be written for use in either parameter 23-10 Maintenance Item or
parameter 23-11 Maintenance Action. The text is written according to the guidelines in parameter 0-37 Display Text 1.
Parameter 23-18 Reset Mechanical Brake Counter
Table 1035: Parameter 23-18 Reset Mechanical Brake Counter
23-18 Reset Mechanical Brake Counter
Default value: [0] Do not reset
Change during operation: True
Select this option to disable the reset of the mechanical brake counter.
Select this option to enable the reset of the mechanical brake counter. After resetting the mechanical
brake counter, the parameter is set to [0] Do not reset, which is the default option.