9-27 Parameter Edit
Option: Function:
Parameters can be edited via Profibus, the standard RS485 interface, or the LCP.
[0] Disabled Disables editing via Profibus.
[1] * Enabled Enables editing via Profibus.
9-28 Process Control
Option: Function:
Process control (setting of Control Word, speed reference, and process data) is possible via either
Profibus or standard fieldbus but not both simultaneously. Local control is always possible via the
LCP. Control via process control is possible via either terminals or fieldbus depending on the settings
in par. 8-50
Coasting Select
to par. 8-56
Preset Reference Select
.
[0] Disable Disables process control via Profibus, and enables process control via standard fieldbus or Profibus
Master class 2.
[1] * Enable cyclic master Enables process control via Profibus Master Class 1, and disables process control via standard field-
bus or Profibus Master class 2.
9-44 Fault Message Counter
Range: Function:
0* [0 - 65535 ] This parameter displays the number of error events stored in par. 9-45
Fault Code
and
par. 9-47
Fault Number
. The maximum buffer capacity is eight error events. The buffer and counter
are set to 0 upon reset or power-up.
9-45 Fault Code
Range: Function:
0* [0 - 0 ] This buffer contains the alarm word for all alarms and warnings that have occurred since last reset
or power-up. The maximum buffer capacity is eight error events.
9-47 Fault Number
Range: Function:
0* [0 - 0 ] This buffer contains the alarm number (e.g. 2 for live zero error, 4 for mains phase loss) for all
alarms and warnings that have occurred since last reset or power-up. The maximum buffer capacity
is eight error events.
9-52 Fault Situation Counter
Range: Function:
0* [0 - 1000 ] This parameter displays the number of error events which have occurred since last reset of power-
up.
9-53 Profibus Warning Word
Range: Function:
0 N/A* [0 - 65535 N/A] This parameter displays Profibus communication warnings. Please refer to the
Profibus Operating
Instructions
for further information.
Read only
FC 300 Programming Guide 3 Parameter descriptions
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
157
3