15-22 Historic Log: Time
Array [50]
Range: Function:
0 ms* [0 -
2147483647
ms]
View the time at which the logged
event occurred. Time is measured in
ms since frequency converter start.
The maximum value corresponds to
approximately 24 days, which
means that the count restarts at 0
after this time period.
4.14.4 15-3* Alarm Log
Parameters in this group are array parameters where up to
10 fault logs can be viewed. 0 is the most recent logged
data, and 9 is the oldest. Fault codes, values, and time
stamp can be viewed for all logged data.
15-30 Fault Log: Error Code
Range: Function:
0* [0 - 65535] View the fault code and look up its
meaning in chapter 6 Trouble-
shooting.
15-31 Alarm Log: Value
Array [10]
Range: Function:
0* [-32767 -
32767 ]
View an extra description of the
error. This parameter is mostly used
with alarm 38, internal fault.
15-32 Alarm Log: Time
Array [10]
Range: Function:
0 s* [0 -
2147483647 s]
View the time when the logged
event occurred. Time is measured in
s from frequency converter start-up.
4.14.5 15-4* Drive Identication
Parameters containing read-only information about the
hardware and software conguration of the frequency
converter.
15-40 FC Type
Range: Function:
0* [0 - 6] View the frequency converter type.
The readout is identical to the FC
300 power eld of the type code
denition, characters 1–6.
15-41 Power Section
Range: Function:
0* [0 - 20] View the frequency converter type.
The readout is identical to the FC
300 power eld of the type code
denition, characters 7–10.
15-42 Voltage
Range: Function:
0* [0 - 20] View the frequency converter type.
The readout is identical to the FC
300 power eld of the type code
denition, characters 11–12.
15-43 Software Version
Range: Function:
0* [0 - 5 ] View the combined SW version (or
package version) consisting of
power SW and control SW.
15-44 Ordered Typecode String
Range: Function:
0* [0 - 40 ] View the type code string used for
reordering the frequency converter
in its original conguration.
15-45 Actual Typecode String
Range: Function:
0* [0 - 40 ] View the actual type code string.
15-46 Frequency Converter Ordering No
Range: Function:
0* [0 - 8 ] View the 8-digit ordering number
used for reordering the frequency
converter in its original congu-
ration. To restore the ordering
number after the power card
exchange, see
parameter 14-29 Service Code.
15-47 Power Card Ordering No
Range: Function:
0* [0 - 8 ] View the power card ordering
number.
15-48 LCP Id No
Range: Function:
0* [0 - 20 ] View the LCP ID number.
15-49 SW ID Control Card
Range: Function:
0* [0 - 20 ] View the control card software
version number.
Parameter Descriptions VLT® AutomationDrive FC 361
142 Danfoss A/S © 03/2019 All rights reserved. MG06J202