5.2.19 22-** Appl. Functions
Param
eter
numb
er
Parameter description Default value 4 set-up Change
during
operation
Conversion
index
Type
22-0* Miscellaneous
22-00 External Interlock Delay 0 s All set-ups TRUE 0 Uint16
22-4* Sleep Mode
22-40 Minimum Run Time 10 s All set-ups TRUE 0 Uint16
22-41 Minimum Sleep Time 10 s All set-ups TRUE 0 Uint16
22-42 Wake-up Speed [RPM] Expressionlimit All set-ups TRUE 0 Uint16
22-43 Wake-up Speed [Hz] Expressionlimit All set-ups TRUE 0 Uint16
22-44 Wake-up Ref./FB Dierence 10 % All set-ups TRUE 0 Int8
22-45 Setpoint Boost 0 % All set-ups TRUE 0 Int8
22-46 Maximum Boost Time 60 s All set-ups TRUE 0 Uint16
22-6* Broken Belt Detection
22-60 Broken Belt Function [0] O All set-ups TRUE Uint8
22-61 Broken Belt Torque 10 % All set-ups TRUE 0 Uint8
22-62 Broken Belt Delay 10 s All set-ups TRUE 0 Uint16
5.2.20 30-** Special Features
Param
eter
numb
er
Parameter description Default value 4 set-up Change
during
operation
Conversion
index
Type
30-2* Adv. Start Adjust
30-20 High Starting Torque Time [s] ExpressionLimit All set-ups TRUE -2 Uint16
30-21 High Starting Torque Current [%] ExpressionLimit All set-ups TRUE -1 Uint32
30-22 Locked Rotor Protection ExpressionLimit All set-ups TRUE Uint8
30-23 Locked Rotor Detection Time [s] ExpressionLimit All set-ups TRUE -2 Uint8
30-24 Locked Rotor Detection Speed Error [%] 25 % All set-ups TRUE -1 Uint32
5.2.21 40-** Special Settings
Param
eter
numb
er
Parameter description Default value 4 set-up Change
during
operation
Conversion
index
Type
40-4* Extend. Fault Log
40-40 Fault Log: Ext. Reference 0 % All set-ups FALSE -1 Int16
40-41 Fault Log: Frequency 0 Hz All set-ups FALSE -1 Uint16
40-42 Fault Log: Current 0 A All set-ups FALSE -2 Int32
40-43 Fault Log: Voltage 0 V All set-ups FALSE -1 Uint16
40-44 Fault Log: DC Link Voltage 0 V All set-ups FALSE 0 Uint16
40-45 Fault Log: Control Word 0 N/A All set-ups FALSE 0 V2
40-46 Fault Log: Status Word 0 N/A All set-ups FALSE 0 V2
Parameter Lists Programming Guide
MG06J202 Danfoss A/S © 03/2019 All rights reserved. 177
5 5

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals