4.6.2 5-3* Digital Outputs
The 2 solid-state digital outputs are common for terminals
27 and 29. Set the I/O function for terminal 27 in 
parameter 5-01 Terminal 27 Mode, and set the I/O function
for terminal 29 in parameter 5-02 Terminal 29 Mode.
NOTICE
These parameters cannot be adjusted while the motor is
running.
[0] No operation Default for all digital outputs and relay
outputs.
[1] Control ready The control card is ready, for example:
Feedback from a frequency converter
controlled by a 24 V external supply (VLT
®
24 V DC Supply MCB 107) and the main
power to the unit is not detected.
[2] Drive ready The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3] Drive ready/
remote
control
The frequency converter is ready for
operation and is in auto-on mode.
[4] Enable/no
warning
Ready for operation. No start or stop
command has been given (start/disable).
No warnings are active.
[5] VLT running The motor runs and shaft torque is
present.
[6] Running/no
warning
The output speed is higher than the speed
set in parameter 1-81 Min Speed for
Function at Stop [RPM]. The motor runs and
there are no warnings.
[7] Run in
range/no
warning
Motor runs within the programmed current
and speed ranges set in
parameter 4-50 Warning Current Low to 
parameter 4-53 Warning Speed High. There
are no warnings.
[8] Run on
reference/no
warning
Motor runs at reference speed. No
warnings.
[9] Alarm An alarm activates the output. There are
no warnings.
[10] Alarm or
warning
An alarm or a warning activates the
output.
[11] At torque
limit
The torque limit set in 
parameter 4-16 Torque Limit Motor Mode or 
parameter 4-17 Torque Limit Generator Mode
has been exceeded.
[12] Out of
current range
The motor current is outside the range set
in parameter 4-18 Current Limit.
[13] Below
current, low
Motor current is lower than set in
parameter 4-50 Warning Current Low.
[14] Above
current, high
Motor current is higher than set in
parameter 4-51 Warning Current High.
[15] Out of speed
range
Output frequency is outside the frequency
range set in parameter 4-52 Warning Speed
Low and parameter 4-53 Warning Speed
High.
[16] Below speed,
low
Output speed is lower than the setting in
parameter 4-52 Warning Speed Low.
[17] Above speed,
high
Output speed is higher than the setting in 
parameter 4-53 Warning Speed High.
[18] Out of
feedback
range
Feedback is outside the range set in
parameter 4-56 Warning Feedback Low and
parameter 4-57 Warning Feedback High.
[19] Below
feedback low
Feedback is below the limit set in
parameter 4-56 Warning Feedback Low.
[20] Above
feedback high
Feedback is above the limit set in
parameter 4-57 Warning Feedback High.
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[22] Ready, no
thermal
warning
Frequency converter is ready for operation,
and there is no overtemperature warning.
[23] Remote,
ready, no
thermal
warning
Frequency converter is ready for operation
and is in auto-on mode. There is no
overtemperature warning.
[24] Ready,
Voltage OK
Frequency converter is ready for operation
and the mains voltage is within the
specied voltage range (see the section
General Specications in the frequency
converter design guide).
[25] Reverse The motor runs (or is ready to run)
clockwise when logic = 0 and counter-
clockwise when logic = 1. The output
changes when the reversing signal is
applied.
[26] Bus OK Active communication (no timeout) via the
serial communication port.
[27] Torque limit &
stop
Use in performing a coast stop and in
torque limit condition. If the frequency
converter has received a stop signal and is
at the torque limit, the signal is logic 0.
[31] Relay 123 Relay is activated when [0] Control word is
selected in parameter group 8-** Communi-
cations and Options.
[35] External
Interlock
[38] Motor
feedback
error
[40] Out of ref
range
Active when the actual speed is outside
settings in parameter 4-52 Warning Speed
Low to parameter 4-55 Warning Reference
High.
[41] Below
reference low
Active when actual speed is below speed
reference setting.
Parameter Descriptions VLT® AutomationDrive FC 361