[42] Above
reference
high
Active when actual speed is above speed
reference setting.
[43] Extended PID
Limit
[45] Bus Ctrl Controls output via bus. The state of the
output is set in parameter 5-90 Digital &
Relay Bus Control. If a bus timeout occurs,
the output state is retained.
[46] Bus ctrl, 1 if
timeout
Controls output via bus. The state of the
output is set in parameter 5-90 Digital &
Relay Bus Control. If a bus timeout occurs,
the output state is set high (on).
[47] Bus ctrl, 0 if
timeout
Controls output via bus. The state of the
output is set in parameter 5-90 Digital &
Relay Bus Control. If a bus timeout occurs,
the output state is set low (o).
[55] Pulse output
[59] Remote,
enable,no TW
[60] Comparator 0 See parameter group 13-1* Comparators. If
comparator 0 is evaluated as true, the
output goes high. Otherwise, it is low.
[61] Comparator 1 See parameter group 13-1* Comparators. If
Comparator 1 is evaluated as true, the
output goes high. Otherwise, it is low.
[62] Comparator 2 See parameter group 13-1* Comparators. If
comparator 2 is evaluated as true, the
output goes high. Otherwise, it is low.
[63] Comparator 3 See parameter group 13-1* Comparators. If
comparator 3 is evaluated as true, the
output goes high. Otherwise, it is low.
[64] Comparator 4 See parameter group 13-1* Comparators. If
comparator 4 is evaluated as true, the
output goes high. Otherwise, it is low.
[65] Comparator 5 See parameter group 13-1* Comparators. If
comparator 5 is evaluated as true, the
output goes high. Otherwise, it is low.
[70] Logic Rule 0 See parameter group 13-4* Logic Rules. If
logic rule 0 is evaluated as true, the output
goes high. Otherwise, it is low.
[71] Logic Rule 1 See parameter group 13-4* Logic Rules. If
logic rule 1 is evaluated as true, the output
goes high. Otherwise, it is low.
[72] Logic Rule 2 See parameter group 13-4* Logic Rules. If
logic rule 2 is evaluated as true, the output
goes high. Otherwise, it is low.
[73] Logic Rule 3 See parameter group 13-4* Logic Rules. If
logic rule 3 is evaluated as true, the output
goes high. Otherwise, it is low.
[74] Logic Rule 4 See parameter group 13-4* Logic Rules. If
logic rule 4 is evaluated as true, the output
goes high. Otherwise, it is low.
[75] Logic Rule 5 See parameter group 13-4* Logic Rules. If
logic rule 5 is evaluated as true, the output
goes high. Otherwise, it is low.
[80] SL Digital
Output A
See parameter 13-52 SL Controller Action.
The output goes high whenever the smart
logic action [38] Set dig. out. A high is
executed. The output goes low whenever
the smart logic action [32] Set dig. out. A
low is executed.
[81] SL Digital
Output B
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [39] Set dig. out. B high is
executed. The input goes low whenever
the smart logic action [33] Set dig. out. B
low is executed.
[82] SL Digital
Output C
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [40] Set dig. out. C high is
executed. The input goes low whenever
the smart logic action [34] Set dig. out. C
low is executed.
[83] SL Digital
Output D
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [41] Set dig. out. D high is
executed. The input goes low whenever
the smart logic action [35] Set dig. out. D
low is executed.
[84] SL Digital
Output E
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [42] Set dig. out. E high is
executed. The input goes low whenever
the smart logic action [36] Set dig. out. E
low is executed.
[85] SL Digital
Output F
See parameter 13-52 SL Controller Action.
The input goes high whenever the smart
logic action [43] Set dig. out. F high is
executed. The input goes low whenever
the smart logic action [37] Set dig. out. F
low is executed.
[120] Local
reference
active
Output is high when
parameter 3-13 Reference Site = [2] Local.
Reference site set
in
parameter 3-13 R
eference Site
Local
reference
active
[120]
Remote
reference
active
[121]
Reference site:
Local
parameter 3-13 Re
ference Site [2]
Local
1 0
Reference site:
Remote
parameter 3-13 Re
ference Site [1]
Remote
0 1
Reference site:
Linked to Hand/
Auto
Parameter Descriptions Programming Guide
MG06J202 Danfoss A/S © 03/2019 All rights reserved. 71