Reference site set
in
parameter 3-13 R
eference Site
Local
reference
active
[120]
Remote
reference
active
[121]
Hand 1 0
Hando
1 0
Autoo
0 0
Auto 0 1
Table 4.12 Local Reference Active
[121] Remote
reference
active
Output is high when
parameter 3-13 Reference Site = [1] Remote
or [0] Linked to hand/auto while the LCP is
in auto-on mode. See Table 4.12.
[122] No alarm Output is high when no alarm is present.
[123] Start
command
active
Output is high when there is an active
start command (that is via digital input bus
connection, hand-on, or auto-on), and no
stop or start command is active.
[124] Running
reverse
Output is high when the frequency
converter runs counterclockwise (the
logical product of the status bits running
AND reverse).
[125] Drive in hand
mode
Output is high when the frequency
converter is in hand-on mode (as indicated
by the LED light above [Hand On]).
[126] Drive in Auto
mode
Output is high when the frequency
converter is in auto-on mode (as indicated
by the LED light above [Auto On]).
[189] External fan
control
The internal logics for the internal fan
control is transferred to this output to
make it possible to control an external fan
(relevant for hp duct cooling).
[193] Sleep Mode The frequency converter/system has turned
into sleep mode. See parameter group
22-4* Sleep Mode.
[194] Broken Belt A broken belt condition has been
detected. This function must be enabled in
parameter 22-60 Broken Belt Function.
[221] IGBT-cooling Use this option for handling the
overcurrent trips. When the frequency
converter detects an overcurrent condition,
it shows alarm 13, Overcurrent and triggers
a reset. If the overcurrent condition occurs
the 3
rd
time in a row, the frequency
converter shows alarm 13, Overcurrent and
initiates a 3-minute delay before the next
reset.
5-30 Terminal 27 Digital Output
Option: Function:
[0] * No operation Functions are described in parameter group
5-3* Digital Outputs.
5-31 Terminal 29 Digital Output
Option: Function:
[0] * No operation Functions are described in parameter group
5-3* Digital Outputs.
5-32 Term X30/6 Digi Out (MCB 101)
Option: Function:
[0] * No operation Functions are described in parameter group
5-3* Digital Outputs.
5-33 Term X30/7 Digi Out (MCB 101)
Option: Function:
[0] * No operation Functions are described in parameter group
5-3* Digital Outputs.
4.6.3 5-4* Relays
Parameters for conguring the timing and the output
functions for the relays.
5-40 Function Relay
Option: Function:
Relay 1 [0], Relay 2 [1].
VLT
®
Extended Relay Card MCB 113:
Relay 3 [2], Relay 4 [3], Relay 5 [4],
Relay 6 [5].
VLT
®
Relay Card MCB 105: Relay 7
[6], Relay 8 [7], Relay 9 [8].
[0] No operation All digital and relay outputs are by
default set to No Operation.
[1] Control Ready The control card is ready, for
example: Feedback from a
frequency converter where the
control is supplied by an external
24 V supply (VLT
®
24 V DC Supply
MCB 107) and the main power to
frequency converter is not detected.
[2] Drive ready The frequency converter is ready to
operate. Mains and control supplies
are OK.
[3] Drive rdy/rem
ctrl
The frequency converter is ready for
operation and is in auto-on mode.
[4] Enable / no
warning
Ready for operation. No start or
stop commands have been applied
(start/disable). No warnings are
active.
[5] Running The motor is running, and shaft
torque is present.
[6] Running / no
warning
Output speed is higher than the
speed set in parameter 1-81 Min
Speed for Function at Stop [RPM].
The motor runs and there are no
warnings.