5-40 Function Relay
Option: Function:
[7] Run in
range/no warn
The motor runs within the
programmed current and the speed
ranges set in
parameter 4-50 Warning Current Low
and parameter 4-53 Warning Speed
High. No warnings.
[8] Run on ref/no
warn
The motor runs at reference speed.
No warnings.
[9] Alarm An alarm activates the output. No
warnings.
[10] Alarm or
warning
An alarm or a warning activates the
output.
[11] At torque limit The torque limit set in
parameter 4-16 Torque Limit Motor
Mode or parameter 4-17 Torque Limit
Generator Mode has been exceeded.
[12] Out of current
range
The motor current is outside the
range set in parameter 4-18 Current
Limit.
[13] Below current,
low
The motor current is lower than set
in parameter 4-50 Warning Current
Low.
[14] Above current,
high
The motor current is higher than
set in parameter 4-51 Warning
Current High.
[15] Out of speed
range
Output speed/frequency is outside
the frequency range set in
parameter 4-52 Warning Speed Low
and parameter 4-53 Warning Speed
High.
[16] Below speed,
low
Output speed is lower than the
setting in parameter 4-52 Warning
Speed Low.
[17] Above speed,
high
Output speed is higher than the
setting in parameter 4-53 Warning
Speed High.
[18] Out of feedb.
range
Feedback is outside the range set
in parameter 4-56 Warning Feedback
Low and parameter 4-57 Warning
Feedback High.
[19] Below
feedback, low
Feedback is below the limit set in
parameter 4-56 Warning Feedback
Low.
[20] Above
feedback, high
Feedback is above the limit set in
parameter 4-57 Warning Feedback
High.
[21] Thermal
warning
Thermal warning turns on when the
temperature exceeds the limit
either in motor, frequency
5-40 Function Relay
Option: Function:
converter, brake resistor, or
connected thermistor.
[22] Ready,no
thermal W
The frequency converter is ready for
operation and there is no overtem-
perature warning.
[23] Remote,ready,
no TW
The frequency converter is ready for
operation and is in auto-on mode.
There is no overtemperature
warning.
[24] Ready, Voltage
OK
The frequency converter is ready for
operation and the mains voltage is
within the specied voltage range
(see the General Specications
section in the design guide).
[25] Reverse The motor runs (or is ready to run)
clockwise when logic = 0 and
counterclockwise when logic = 1.
The output changes as soon as the
reversing signal is applied.
[26] Bus OK Active communication (no timeout)
via the serial communication port.
[27] Torque limit &
stop
Use for performing a coasted stop
in a torque limit condition. If the
frequency converter has received a
stop signal and is in torque limit,
the signal is logic 0.
[31] Relay 123 Digital output/relay is activated
when [0] Control Word is selected in
parameter group 8-** Comm. and
Options.
[35] External
Interlock
[36] Control word
bit 11
Activate relay 1 by control word
from eldbus. No other functional
impact in the frequency converter.
Typical application: Controlling
auxiliary device from eldbus. The
function is valid when [0] FC prole
in parameter 8-10 Control Word
Prole is selected.
[37] Control word
bit 12
Activate relay 2 by control word
from eldbus. No other functional
impact in the frequency converter.
Typical application: Controlling
auxiliary device from eldbus. The
function is valid when [0] FC prole
in parameter 8-10 Control Word
Prole is selected.
[38] Motor
feedback error
Failure in the speed feedback loop
from motor running in closed loop.
The output can eventually be used
Parameter Descriptions Programming Guide
MG06J202 Danfoss A/S © 03/2019 All rights reserved. 73