5-42   O Delay, Relay
Array[20]
Range: Function:
0.01 s*   [0.01 - 600 s] Enter the delay of the relay cutout
time. Select 1 of 2 internal
mechanical relays in an array
function. See
parameter 5-40 Function Relay for
details. If the selected event
condition changes before a delay
timer expires, the relay output is
unaected.
Selected
Event
Relay
output
On Delay
P 5-41
O Delay
P 5-42
130BA172.10
Illustration 4.27 O Delay, Relay
If the selected event condition changes before the on
delay or o delay timer expires, the relay output is
unaected.
4.6.4 5-5* Pulse Input
The pulse input parameters are used to dene an
appropriate window for the impulse reference area by
conguring the scaling and lter settings for the pulse
inputs. Input terminals 29 or 33 act as frequency reference
inputs. Set terminal 29 (parameter 5-13 Terminal 29 Digital
Input) or terminal 33 (parameter 5-15 Terminal 33 Digital
Input) to [32] Pulse input. If terminal 29 is used as an input,
set parameter 5-01 Terminal 27 Mode to [0] Input.
130BA076.10
(RPM)
Ref.
Low freq.
P 5-50/
P 5-55
Input
(Hz)
High
ref.
value
P 5-53/
p 5-58
High freq.
P 5-51/
P 5-56
Low
ref.
value
P 5-52/
p 5-57
Illustration 4.28 Pulse Input
5-50   Term. 29 Low Frequency
Range: Function:
100 Hz*   [0 - 110000
Hz]
Enter the low frequency limit
corresponding to the low motor
shaft speed (that is low reference
value) in parameter 5-52 Term. 29
Low Ref./Feedb. Value. Refer to
Illustration 4.28.
5-51   Term. 29 High Frequency
Range: Function:
Size
related*
  [0 - 110000
Hz]
Enter the high frequency limit
corresponding to the high motor
shaft speed (that is high reference
value) in parameter 5-53 Term. 29
High Ref./Feedb. Value.
5-52   Term. 29 Low Ref./Feedb. Value
Range: Function:
0 Referen-
ceFeedback
Unit*
  [-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the low reference value limit
for the motor shaft speed [RPM].
This is also the lowest feedback
value, see also parameter 5-57 Term.
33 Low Ref./Feedb. Value. Set
terminal 29 to digital input
(parameter 5-02 Terminal 29 Mode =
[0] input (default) and
parameter 5-13 Terminal 29 Digital
Input = applicable value).
5-53   Term. 29 High Ref./Feedb. Value
Range: Function:
Size
related*
  [-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the high reference value
[RPM] for the motor shaft speed
and the high feedback value, see
also parameter 5-58 Term. 33 High
Ref./Feedb. Value. Select terminal 29
as a digital input
(parameter 5-02 Terminal 29 Mode =
[0] input (default) and
parameter 5-13 Terminal 29 Digital
Input = applicable value).
5-54   Pulse Filter Time Constant #29
Range: Function:
100
ms*
  [5 - 1000
ms]
Enter the pulse lter time constant. The
pulse lter dampens oscillations of the
feedback signal. If there is much noise in
the system, this is an advantage. A high
time constant value results in better
dampening but also increases the time
delay through the lter.
Parameter Descriptions VLT® AutomationDrive FC 361
76 Danfoss A/S © 03/2019 All rights reserved. MG06J202