4.6.5 5-7* 24 V Encoder Input
Connect the 24 V encoder to terminal 12 (24 V DC supply),
terminal 32 (channel A), terminal 33 (channel B), and
terminal 20 (GND). The digital inputs 32/33 are active for
encoder inputs when [1] 24 V encoder is selected in
parameter 7-00 Speed PID Feedback Source. The encoder
used is a dual-channel (A and B) 24 V type. Maximum
input frequency: 110 kHz.
Encoder connection to the frequency converter
24 V incremental encoder. Maximum cable length is 5 m
(16.4 ft).
e30bg758.10
+24 V DC
A
B
GND
13
12
18
32
27
19
29
33
20
24 V or 10–30 V encoder
Illustration 4.30 Encoder Connection
B
A
B
A
130BA646.10
CW
CCW
Illustration 4.31 Encoder Rotation Direction
5-70 Term 32/33 Pulses Per Revolution
Range: Function:
1024* [1 - 4096] Set the encoder pulses per
revolution on the motor shaft. Read
the correct value from the encoder.
5-71 Term 32/33 Encoder Direction
Option: Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Change the detected encoder
rotation direction without changing
the wiring to the encoder.
[0] * Clockwise Sets channel A 90° (electrical
degrees) behind channel B upon
clockwise rotation of the encoder
shaft.
[1] Counter
clockwise
Sets channel A 90° (electrical
degrees) ahead of channel B upon
clockwise rotation of the encoder
shaft.
Parameter Descriptions Programming Guide
MG06J202 Danfoss A/S © 03/2019 All rights reserved. 79
4 4