8-08 Readout Filtering
Use this function if the speed feedback value readouts on the
eldbus uctuate. Select [1] Motor Data LP-Filter if the function is
required. A power cycle is required for changes to take eect.
Option: Function:
[1] Motor Data
LP-Filter
Filtered eldbus readouts of the
following parameters:
Parameter 16-10 Power
[kW].
Parameter 16-11 Power
[hp].
Parameter 16-12 Motor
Voltage.
Parameter 16-14 Motor
current.
Parameter 16-16 Torque
[Nm].
Parameter 16-17 Speed
[RPM].
Parameter 16-22 Torque
[%].
Parameter 16-25 Torque
[Nm] High.
4.9.2 8-1* Ctrl. Word Settings
8-10 Control Word Prole
Select the interpretation of the control and status words
corresponding to the installed eldbus. Only the selections valid
for the eldbus installed in slot A are visible in the LCP display.
For guidelines in selection of [0] FC prole and [1] PROFIdrive
prole, refer to the design guide.
For more guidelines in the selection of [1] PROFIdrive prole, refer
to the installation guide for the installed eldbus.
Option: Function:
[0] * FC prole
[1] PROFIdrive
prole
8-13 Congurable Status Word STW
This is an array parameter with 16 elements, 1 element for each
bit in range 0–15. Elements 5 and 11–15 are congurable. Each
of the bits can be congured to any of the following options.
Option: Function:
[0] No function The input is always low.
[1] * Prole Default Depending on the prole set
in parameter 8-10 Control
Prole.
[2] Alarm 68 Only The input goes high
whenever alarm 68, Safe
Torque O activated is active
and goes low whenever
alarm 68, Safe Torque O
activated is not active.
[3] Trip excl Alarm 68
[10] T18 DI status
[11] T19 DI status
[12] T27 DI status
[13] T29 DI status
[14] T32 DI status
[15] T33 DI status
[21] Thermal warning
[40] Out of ref range
[49] Derate active
[60] Comparator 0
[61] Comparator 1
[62] Comparator 2
[63] Comparator 3
[64] Comparator 4
[65] Comparator 5
[70] Logic Rule 0
[71] Logic Rule 1
[72] Logic Rule 2
[73] Logic Rule 3
[74] Logic Rule 4
[75] Logic Rule 5
[80] SL digital out A
[81] SL digital out B
[82] SL digital out C
[83] SL digital out D
[84] SL digital out E
[85] SL digital out F
[92] IGBT-cooling See parameter group 5-3*
Digital Outputs.
[193] Sleep Mode
[194] Broken Belt
Parameter Descriptions Programming Guide
MG06J202 Danfoss A/S © 03/2019 All rights reserved. 95
4 4

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals