EasyManuals Logo

Danfoss VLT AutomationDrive Manual

Danfoss VLT AutomationDrive
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
VLT
®
AutomationDrive EtherNet/IP
– H o w t o C o n t r o l t h e F C 3 0 0 –
MG.90.Jx.02 ver. 5
th
September 2007 – VLT is a registered Danfoss trademark 29
Status Word under Instances 20/70 and
21/71
The status word in Instances 70 and 71 is
defined as follows:
Slave master
STW Actual RPM
Bit
no.:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Note that the bits 00 and 02 in Instance 70 are
identical with bits 00 and 02 in the more
extensive Instance 71.
Instance 70
Instance 71
Bit
Bit = 0 Bit =1 Bit = 0 Bit =1
00 - Fault
-
Fault
01 - -
-
Warning
02 -
Running
1 Fwd
- Running
1 Fwd
03 - -
- Running
2 Rev.
04 - -
-
Ready
05 - -
- Ctrl from
Net
06 - -
- Ref.
from Net
07 - - - At ref.
08-
15
- - State Attribute
Explanation of the Bits:
Bit 0, Fault
:
Bit 0 = "0" means that there is no fault in the
frequency converter.
Bit 0 = "1" means that there is a fault in the
frequency converter.
Bit 1, Warning
:
Bit 0 = "0" means that there is no unusual
situation.
Bit 0 = "1" means that an abnormal condition
has occurred.
Bit 2, Running 1
:
Bit 2 = "0" means that the drive is not in one
of these states or that Run 1 is not set.
Bit 2 = "1" means that the drive state attribute
is enabled or stopping, or that Fault-Stop and
bit 0 (Run 1) of the control word are set at the
same time.
Bit 3, Running 2
:
Bit 3 = "0" means that the drive is in neither of
these states or that Run 2 is not set.
Bit 3 = "1" means that the drive state attribute
is enabled or stopping, or that fault-stop and
bit 0 (Run 2) of the control word are set at the
same time.
Bit 4, Ready
:
Bit 4 = "0" means that the state attribute is in
another state.
Bit 4 = "1" means that the state attribute is
ready, enabled or stopping.
Bit 5, Control from net:
Bit 5 = "0" means that the drive is controlled
from the standard inputs.
Bit 5 = "1" means that EIP has control (start,
stop, reverse) of the drive.
Bit 6, Ref from net:
Bit 6 = "0" means that the reference comes
from inputs to the drive.
Bit 6 = "1" means that the reference comes
from EIP.
Bit 7, At reference:
Bit 7 = "0" means that the motor is running,
but that the present speed is different from the
preset speed reference, i.e. the speed is being
ramped up/down during start/stop.
Bit 7 = "1" means that the drive and reference
speeds are equal.
Bit 8 - 15, State attribute:
(Instance 71 only)
Represents the state attribute of the drive, as
indicated in the following table:
Bit
Number
Meaning
8 (Vendor specific)
9 Start up
10 Not ready
11 Ready
12 Enabled
13 Stopping
14 Fault stop
15 Faulted
For more detail of the actual output speed, see
the section Actual output speed under
Instances 20/70 and 21/71.

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals