EasyManuals Logo

Danfoss VLT AutomationDrive Manual

Danfoss VLT AutomationDrive
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
VLT
®
AutomationDrive EtherNet/IP
- H o w t o C o n t r o l t h e F C 3 0 0 -
MG.90.Jx.02 ver. 5
th
September 2007 – VLT is a registered Danfoss trademark 28
ODVA Control Profile
Control Word under Instances 20/70 and
21/71
Set parameter 8-10 Control Word Profile to
ODVA, and select the instance in parameter
10-10 Process Data Type Selection.
The control word in Instances 20 and 21 is
defined as follows:
Master slave
CTW Speed ref. RPM
Bit
no.:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
N.B.:
Note that the bits 00 and 02 in Instance
20 are identical with bits 00 and 02 in the
more extensive Instance 21.
Instance 20
Instance 21
Bit
Bit = 0 Bit =1 Bit = 0 Bit =1
00 Stop
Run
Fwd
Stop
Run
Fwd
01 - -
Stop Run Rev
02
No
function
Fault
reset
No
function
Fault
reset
03
- - - -
04
- - - -
05
- - - Net Ctrl
06
- - - Net Ref
07-
15
- - - -
Explanation of the Bits:
Bit 0, Run Fwd:
Bit 0 = "0" means that the VLT frequency
converter has a stop command.
Bit 0 = "1" leads to a start command and the
VLT frequency converter will start to run the
motor clockwise.
Bit 1, Run Rev
:
Bit 1 = "0" leads to a stop of the motor.
Bit 1 = "1" leads to a start of the motor.
Bit 2, Fault Reset
:
Bit 2 = "0" means that there is no reset of a
trip.
Bit 2 = "1" means that a trip is reset.
Bit 3, No function:
Bit 3 has no function.
Bit 4, No function:
Bit 4 has no function.
Bit 5, Net Control
:
Bit 5 = "0" means that the drive is controlled
from the standard inputs.
Bit 5 = "1" means that EIP controls the drive.
N.B.:
Please note that changes will affect
parameters 8-50 to 8-56.
Bit 6, Net Reference
:
Bit 6 = "0" Reference is from the standard
inputs.
Bit 6 = "1" Reference is from EIP.
N.B.:
Please note that changes will affect
parameters 3-15 to 3-17 Reference source
X.
For the Speed reference, see section Bus speed
reference value under Instances 20/70 and
21/71.

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals