26-44 Terminal X42/7 Timeout Preset
Range: Function:
0 %* [0 - 100 %] Holds the preset level of terminal X42/7.
In
case of a bus timeout and a timeout
function is selected in 26-50 Terminal X42/9
Output the output will preset to this level.
3.20.6 26-5* Analog Input X42/9
26-50 Terminal X42/9 Output
Option: Function:
Set the function of terminal X42/9.
[0] * No operation
[100] Output frequency 0-100 Hz, (0-20 mA)
[101] Reference Minimum reference - Maximum
reference,
(0-20 mA)
[102] Feedback
-200% to +200% of 3-03
Maximum
Reference, (0-20 mA)
[103] Motor Current
0 - Inverter Max. Current (16-37
Inv.
Max. Current), (0-20 mA)
[104] Torque rel to limit
0 - Torque limit (4-16
Torque Limit
Motor Mode), (0-20 mA)
[105] Torq relate to
rated
0 - Motor rated torque, (0-20 mA)
[106] Power 0 - Motor rated power, (0-20 mA)
[107] Speed
0 - Speed High Limit (4-13
Motor
Speed High Limit [RPM] and 4-14 Motor
Speed High Limit [Hz]), (0-20 mA)
[108] Torque
[109] Max Out Freq
[113] Ext. Closed Loop 1 0 - 100%, (0-20 mA)
[114] Ext. Closed Loop 2 0 - 100%, (0-20 mA)
[115] Ext. Closed Loop 3 0 - 100%, (0-20 mA)
[139] Bus ctrl. 0 - 100%, (0-20 mA)
[141] Bus ctrl t.o. 0 - 100%, (0-20 mA)
26-51 Terminal X42/9 Min. Scale
Range: Function:
0 %* [0 - 200
%]
Scale the minimum output of the selected
analog
signal at terminal X42/9, as a percentage
of the maximum signal level. E.g. if a 0 V is
desired at 25% of the maximum output value.
Then programme 25%. Scaling values up to
100% can never be higher than the
corresponding setting in 26-52 Terminal X42/9
Max. Scale.
See principle graph for 6-51
Terminal 42 Output Min Scale.
26-52 Terminal X42/9 Max. Scale
Range: Function:
100
%*
[0 -
200
%]
Scale the maximum output of the selected analog
signal
at terminal X42/9. Set the value to the
maximum value of the voltage signal output. Scale
the output to give a voltage lower than 10 V at
full scale; or 10 V at an output below 100% of the
maximum signal value. If 10 V is the desired
output current at a value between 0-100% of the
full-scale output, programme the percentage value
in the parameter, i.e. 50% = 10 V. If a voltage
between 0 and 10V is desired at maximum output,
calculate the percentage as follows:
i.e.
5
V
:
10
V
5
V
x
100 % = 200 %
See principle graph for 6-52
Terminal 42 Output Max Scale.
26-53 Terminal X42/9 Bus Control
Range: Function:
0 %* [0 - 100 %] Holds the level of terminal X42/9 if
controlled
by bus.
26-54 Terminal X42/9 Timeout Preset
Range: Function:
0 %* [0 - 100 %] Holds the preset level of terminal X42/9.
In
case of a bus timeout and a timeout
function is selected in 26-60 Terminal X42/11
Output the output will preset to this level.
3.20.7 26-6* Analog Input X42/11
26-60 Terminal X42/11 Output
Option: Function:
Set the function of terminal X42/11.
[0] * No operation
[100] Output frequency 0-100 Hz, (0-20 mA)
[101] Reference Minimum reference - Maximum
reference,
(0-20 mA)
[102] Feedback
-200% to +200% of 3-03
Maximum
Reference, (0-20 mA)
[103] Motor Current
0 - Inverter Max. Current (16-37
Inv.
Max. Current), (0-20 mA)
[104] Torque rel to limit
0 - Torque limit (4-16
Torque Limit
Motor Mode), (0-20 mA)
[105] Torq relate to rated 0 - Motor rated torque, (0-20 mA)
[106] Power 0 - Motor rated power, (0-20 mA)
[107] Speed
0 - Speed High Limit (4-13
Motor
Speed High Limit [RPM] and 4-14 Motor
Speed High Limit [Hz]), (0-20 mA)
[108] Torque
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
162 MG16H102 - VLT
®