EasyManuals Logo
Home>Danfoss>DC Drives>VLT FC 103

Danfoss VLT FC 103 Programming Guide

Danfoss VLT FC 103
203 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
8-05 End-of-Timeout Function
Option: Function:
[0] Hold set-up
Retains the set-up selected in 8-04
Control
Timeout Function and displays a warning, until
8-06 Reset Control Timeout toggles. Then the
frequency converter resumes its original set-
up.
[1] * Resume set-
up
Resumes the set-up active before the time-
out.
8-06 Reset Control Timeout
Option: Function:
This parameter is active only when the choice [0]
Hold
set-up has been selected in 8-05 End-of-
Timeout Function.
[0] * Do not
reset
Retains the set-up specified in 8-04
Control
Timeout Function, [7] Set-up 1, [8] Set-up 2, [9] Set-
up 3 and [10] Set-up 4 following a control time-
out.
[1] Do
reset
Returns the frequency converter to the original
set-up
following a control word time-out. When
the value is set to [1] Do reset, the frequency
converter performs the reset and then
immediately reverts to the [0] Do not reset setting.
8-07 Diagnosis Trigger
Option: Function:
This parameter has no function for
BACnet.
[0] * Disable
[1] Trigger on alarms
[2] Trigger alarm/warn.
3.9.3 8-1* Ctrl. Word Settings
8-10 Control Profile
Option: Function:
Select the interpretation of the control
and
status words corresponding to the
installed fieldbus. Only the selections
valid for the fieldbus installed in slot A
will be visible in the LPC display.
[0] * FC profile
[1] PROFIdrive profile
[5] ODVA
[7] CANopen DSP 402
8-13 Configurable Status Word STW
Option: Function:
This parameter enables configuration of bits
12–15
in the status word.
[0] No function
8-13 Configurable Status Word STW
Option: Function:
[1] * Profile
Default
Function corresponds to the profile default
selected
in 8-10 Control Profile.
[2] Alarm 68
Only
Only set in case of an Alarm 68.
[3] Trip excl.
Alarm
68
Set in case of a trip, except if Alarm 68
executes the trip.
[10] T18 DI
status.
The bit indicates the status of terminal 18.
“0”
indicates that the terminal is low
“1” indicates that the terminal is high
[11] T19 DI
status.
The bit indicates the status of terminal 19.
“0”
indicates that the terminal is low
“1” indicates that the terminal is high
[12] T27 DI
status.
The bit indicates the status of terminal 27.
“0”
indicates that the terminal is low
“1” indicates that the terminal is high
[13] T29 DI
status.
The bit indicates the status of terminal 29.
“0”
indicates that the terminal is low
“1” indicates that the terminal is high
[14] T32 DI
status.
The bit indicates the status of terminal 32.
“0”
indicates that the terminal is low
“1” indicates that the terminal is high
[15] T33 DI
status.
The bit indicates the status of terminal 33.
“0”
indicates that the terminal is low
“1” indicates that the terminal is high
[16] T37 DI
status
The bit indicates the status of terminal 37.
0”
indicates T37 is low (safe stop)
“1” indicates T37 is high (normal)
[21] Thermal
warning
The thermal warning turns on when the
temperature
exceeds the limit in the motor,
the frequency converter, the brake resistor,
or the thermistor.
[30] Brake fault
(IGBT)
Output is Logic ‘1’ when the brake IGBT is
short-circuited.
Use this function to protect
the frequency converter if there is a fault on
the brake modules. Use the output/relay to
cut out the main voltage from the frequency
converter.
[40] Out of ref.
range
[60] Comtor 0 See parameter group 13-1*. If Comtor 0 is
evaluated
as TRUE, the output goes high.
Otherwise, it is low.
[61] Comtor 1 See parameter group 13-1*. If Comtor 1 is
evaluated
as TRUE, the output goes high.
Otherwise, it is low.
[62] Comtor 2 See parameter group 13-1*. If Comtor 2 is
evaluated
as TRUE, the output goes high.
Otherwise, it is low.
[63] Comtor 3 See parameter group 13-1*. If Comtor 3 is
evaluated
as TRUE, the output goes high.
Otherwise, it is low.
[64] Comtor 4 See parameter group 13-1*. If Comtor 4 is
evaluated
as TRUE, the output goes high.
Otherwise, it is low.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark
79
3 3

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals