Parameters
130BD067.11
FC
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
18
19
20
27
29
32
33
31
50
53
54
55
42
45
A OUT
Function Setting
5-11 Terminal 19
Digital Input
[1] Reset
* = Default Value
Notes/comments:
Table 4.5 External Alarm Reset
Parameters
130BB068.11
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
18
19
20
27
29
32
33
31
50
53
54
55
42
5kΩ
FC
45
A OUT
Function Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53
High Voltage
10 V*
6-14 Terminal 53
Low Ref./Feedb.
Value
0
6-15 Terminal 53
High Ref./Feedb.
Value
1500
6-19 Terminal 53
Mode
[1] voltage
* = Default Value
Notes/comments:
Table 4.6 Speed Reference (Using a Manual Potentiometer)
Parameters
FC
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
R1R2
12
18
19
20
27
29
32
33
31
50
53
54
55
42
01
02
03
04
05
06
130BD150.11
45
A OUT
Function Setting
4-30 Motor
Feedback Loss
Function
[1] Warning
4-31 Motor
Feedback Speed
Error
100
4-32 Motor
Feedback Loss
Timeout
5 s
7-00 Speed PID
Feedback Source
[2] MCB 102
17-11 Resolution
(PPR)
1024*
13-00 SL
Controller Mode
[1] On
13-01 Start Event
[19] Warning
13-02 Stop Event
[44] Reset
key
13-10 Comparato
r Operand
[21] Warning
no.
13-11 Comparato
r Operator
[1] ≈*
13-12 Comparato
r Value
90
13-51 SL
Controller Event
[22]
Comparator 0
13-52 SL
Controller Action
[32] Set
digital out A
low
5-40 Function
Relay
[80] SL digital
output A
* = Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 will be issued. The SLC
monitors Warning 90 and in
the case that Warning 90
becomes TRUE then Relay 1 is
triggered.
External equipment may then
indicate that service may be
required. If the feedback error
goes below the limit again
within 5 s, the frequency
converter continues and the
warning disappears. But Relay 1
will still be triggered until
pressing [Off/Reset].
Table 4.7 Using SLC to Set a Relay
Application Examples
VLT
®
AutomationDrive FC 360 Design Guide
60 MG06B202 - VLT
®
is a registered Danfoss trademark
44