4.4. Quick Menu Parameters
4.4.1. Quick Menu Parameters - Basic Settings QM1
Below are descriptions of all parameters found in the Quick Menu.
* = Factory setting.
1-20 Motor Power [kW]/[HP] (P
m.n
)
Range: Function:
Enter motor power from nameplate data.
[0.09 kW/0.12 HP -
11 kW/15 HP]
Two sizes down, one size up from nominal VLT rating.
NB!
Changing this parameter affects par. 1-22 to 1-25,
1-30, 1-33 and 1-35.
1-22 Motor Voltage (U
m.n
)
Range: Function:
230/400
V
[50 - 999 V] Enter motor voltage from nameplate data.
1-23 Motor Frequency (f
m.n
)
Range: Function:
50 Hz
*
[20-400 Hz] Enter motor frequency from nameplate data.
1-24 Motor Current (I
m.n
)
Range: Function:
M-type
depend-
ent
*
[0.01 - 26.00 A] Enter motor current from nameplate data.
1-25 Motor Nominal Speed (n
m.n
)
Range: Function:
M-type
Depend-
ent
*
[100 - 9999 RPM] Enter motor nominal speed from nameplate data.
1-29 Automatic Motor Tuning (AMT)
Option: Function:
Use AMT to optimize motor performance.
NB!
This parameter cannot be changed while motor
runs.
4. Programming VLT Micro Drive FC 51 Operating Instructions
18
MG.02.A2.02 - VLT
®
is a registered Danfoss trademark