EasyManuals Logo

Danfoss VLT Micro Drive FC 51 Operating Instructions

Danfoss VLT Micro Drive FC 51
37 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
Leakage Current
The earth leakage current from the VLT Micro Drive FC 51 exceeds 3.5 mA. According
to IEC 61800-5-1 a reinforced Protective Earth connection must be ensured by
means of a min. 10mm² Cu or an addtional PE wire - with the same cable cross
section as the Mains wiring - must be terminated separately.
Residual Current Device
This product can cause a D.C. current in the protective conductor. Where a residual
current device (RCD) is used for extra protection, only an RCD of Type B (time de-
layed) shall be used on the supply side of this product. See also Danfoss Application
Note on RCD, MN.90.GX.YY.
Protective earthing of the VLT Micro Drive and the use of RCDs must always follow
national and local regulations.
Motor overload protection is possible by setting Parameter 1-90 Motor thermal pro-
tection to the value ETR trip. For the North American market: ETR functions provide
class 20 motor overload protection, in accordance with NEC.
Installation in high altitudes:
By altitudes above 2km, please contact Danfoss Drives regarding PELV.
1.1.5. IT Mains
IT Mains
Installation on isolated mains source, i.e. IT mains.
Max. supply voltage allowed when connected to mains: 440 V.
As an option, Danfoss offers line filters for improved harmonics performance.
1.1.6. Avoid unintended Start
While the frequency converter is connected to mains, the motor can be started/stopped using
digital commands, bus commands, references or via the Local Control Panel.
Disconnect the frequency converter from mains whenever personal safety considerations
make it necessary to avoid unintended start of any motors.
To avoid unintended start, always activate the [OFF] key before changing parameters.
1.1.7. Disposal Instruction
Equipment containing electrical components must not be disposed of
together with domestic waste.
It must be separately collected with electrical and electronic waste
according to local and currently valid legislation.
1. Safety VLT Micro Drive FC 51 Operating Instructions
4
MG.02.A2.02 - VLT
®
is a registered Danfoss trademark
1

Other manuals for Danfoss VLT Micro Drive FC 51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Specifications

General IconGeneral
EnclosureIP20
Output Voltage0-100% of supply voltage
AltitudeUp to 1000 m without derating
Power Range0.18-22 kW
Control MethodV/f
CommunicationModbus RTU
Protection FeaturesOver-voltage, under-voltage, over-current, over-temperature
Ambient Temperature-10°C to 50°C
Storage Temperature-25°C to 65°C
Relative Humidity5-95% (non-condensing)
Input Voltage200-240 V, 380-480 V
Braking FunctionIntegrated braking chopper (optional)

Related product manuals