EasyManuals Logo
Home>Danfoss>DC Drives>VLT Micro Drive FC 51

Danfoss VLT Micro Drive FC 51 Operating Instructions

Danfoss VLT Micro Drive FC 51
37 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
For altitudes above 2000 m, please contact Danfoss Drives regarding PELV.
Below 1000 m altitude no de-rating is necessary but above 1000 m the ambient temperature or
the maximum output current should be decreased.
Decrease the output by 1% per 100 m altitude above 1000 m or reduce the max. ambient tem-
perature by 1 degree per 200 m
7.3.4. Derating for Running at Low Speeds
When a motor is connected to at frequency converter, it is necessary to check that the cooling of
the motor is adequate.
A problem may occur at low speeds in constant torque applications. Running continuously at low
speeds – below half the nominal motor speed – may require additional air cooling. Alternatively,
choose a larger motor (one size up).
7. Specifications VLT Micro Drive FC 51 Operating Instructions
34
MG.02.A2.02 - VLT
®
is a registered Danfoss trademark
7

Other manuals for Danfoss VLT Micro Drive FC 51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive FC 51
CategoryDC Drives
LanguageEnglish

Related product manuals