6-25 Terminal 60 High Feedback Value
Range: Function:
[-4999 - 4999] Value corresponding to P. 6-23 setting.
6-26 Terminal 60 Filter Time Constant
Range: Function:
[0.01 - 10.00 s] Noise suppressing filter.
7-20 Process CL Feedback Resource
Range: Function:
[] Choose [2] analog input 60.
7-30 Process PI Normal/Inverse
Range: Function:
[] Most PI controllers are “Normal”.
7-31 Process PI Anti Windup
Range: Function:
[] Leave
Enabled
normally.
7-32 Process PI Start Speed
Range: Function:
[0.0 - 200.0 Hz] Choose expected normal running speed.
7-33 Process PI Proportional Gain
Range: Function:
[0.00 - 10.00] Enter the P-factor.
7-34 Process PI Integral Time
Range: Function:
[0.10 - 9999.00 s] Enter the I-factor.
7-38 Process Feed Forward Factor
Range: Function:
[0 - 400%] Only applicable with changing set-points.
VLT Micro Drive FC 51 Operating Instructions 4. Programming
MG.02.A2.02 - VLT
®
is a registered Danfoss trademark