5 Commissioning
5.1 Before Commissioning
5.1.1 Safety Guidelines
When commissioing/decommissioning:
• Secure the site in accordance with regulations (barrier, warnings, signs, and more). Only qualified personnel is allowed to
commission/recommission the system.
• Refer to the guidelines, information, and specifications stated in the operating guide of the relevant programmable control system.
• Make sure that no personal injury and/or material damage can occur, even if the plant/machine moves unintentionally.
CAUTION
ELECTROSTATIC DISCHARGE
Electrostatic discharge can damage components.
-
Ensure discharge before touching the safety option, for example by touching a grounded, conductive surface or by wearing
a grounded armband.
WARNING
RISK OF ELECTROCUTION
Wiring the electrical connections on the drive while voltage is applied can lead to death or serious injury.
-
Switch off power.
-
Make sure that the control cabinet is provided with an access lock or warning signs.
-
DO NOT switch on voltage until the system is commissioned.
Refer to the VLT® AutomationDrive FC 301/FC 302 Operating Guide for further information on the drive. Refer to the VLT® Motion
Control Tool MCT 10 Operating Guide for further information on the Safe Plug-in.
5.1.2 Commissioning Requirements
Context:
Observe the following:
• When setting up the option for the 1
st
time, ensure to have a commissioning report at hand, see further information in the VLT®
Motion Control Tool MCT 10 Operating Guide.
NOTICE
Only LCP SW version 7.0 or newer is supported.
Prerequisites:
The following components are required to perform the necessary steps for commissioning the safety option:
Commissioning
Installation Guide | VLT® Safety Option MCB 150/151
AQ279747441421en-000101 / 130R0292
52 | Danfoss A/S © 2018.09