9.4.3 Reset Characteristics
Manual reset time ≤5 ms (safety option), ≤5 ms (drive), ≤10 ms (fieldbus)
Manual reset pulse time 10 µs (safety option and drive)
Automatic reset time ≤4 ms
Start-up reset time ≤5 s (parameter 42-90 Restart Safe Option)
9.4.4 Response Time
Input to output response time ≤2 ms
Emergency stop until beginning of SS1/SLS ≤7 ms
Cross fault detection time ≤3 ms (@activated output)
9.4.5 Safety Characteristic Data
NOTICE
The safety-related characteristic data are valid for all safety functions. All units used within a safety function must be considered
when calculating the safety characteristic data.
Table 34: European Directives
Name of directive Number/Description
Machinery Directive (2006/42/EC) EN ISO 13849-1
EN IEC 62061
EN IEC 61800-5-2
EMC Directive (2004/108/EC) EN 50011
EN 61000-6-3
EN 61800-3
Low Voltage Directive (2006/95/EC) EN 50178
EN 61800-5-1
Table 35: Safety Standards
Name of standard Number/description
Safety of Machinery EN ISO 13849-1
IEC 62061
IEC 60204-1
Functional Safety IEC 61508-1 to -7
IEC 61800-5-2