7.4.1 Safety Guidelines
When commissioning/recommissioning, note the following:
Secure the site in accordance with the regulations (barrier, warning signs, and more). The system may only be commissioned/
recommssioned by qualified personnel.
Refer to the information and specifications stated in the operating guide of the relevant programmable control system.
During commissioning/recommissioning, make sure that no personal injury and/or material damage can occur, even if the plant/
machine moves unintentionally.
When commissioning the safety option, read the safety guidelines in the operating guide for the drive.
7.4.2 Before Running the Commissioning Test
The system integrator/machine manufacturer runs a commissioning test of the safety option to verify and document the correct
selection of the safety option parameter values. The system integrator/machine manufacturer hereby proves to have tested the
effectiveness of the safety functions used. Run the commissioning test based on the risk analysis. All applicable standards and
regulations must be adhered to.
Check that:
The machine is properly wired.
The effectiveness of all safety components used in the application fulfills the requirements.
All safety equipment, such as protective door monitoring devices, light barriers, or emergency stop switches, is connected and
ready for operation.
All motor parameters and command parameters must be set correctly on the drive.
Run a commissioning test of the safety option in the following situations:
After the configuration of each machine.
After changing the safety option parameters.
After making changes to the machine (as per applicable standards and regulations).
7.4.2.1 Checking Effectiveness of Safety Functions
Procedure
1. Document each individual step of the test.
2. Note the checksum of the safety option parameters in the records.
3. Do NOT release the system unless it has successfully passed all individual steps of the test.
4. Restart the drive and check that the motor runs normally.
7.4.3 Safety Functions in the Drive
After making, for example, LCP copy of safe parameters, a commissioning test is required. Use these short versions of the
commissioning test reports to follow and approve the test sequence.
Service and Repair
Installation Guide | VLT® Safety Option MCB 150/151
AQ279747441421en-000101 / 130R0292 | 75
Danfoss A/S © 2018.09

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Safety Option MCB 150 and is the answer not in the manual?

Danfoss VLT Safety Option MCB 150 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Safety Option MCB 150
CategoryControl Unit
LanguageEnglish

Related product manuals