Message Description
SO Custom. aborted
SO RESET required!
!1(1)
Press [Cancel] to abort the customization of the safety option. A reset is required to finalize this
procedure.
Illustration 40: Possible Parameter Set-up
7.4 Commissioning Test
The commissioning test for systems with safety functions is focused on validating the functionality of safety monitoring and stop
functions configured in the drive system.
The test objective is to verify proper configuration of the defined safety functions and of test mechanisms and to examine the response
of specific monitoring functions to the explicit input of values outside tolerance limits. Test safety-configured monitoring functions
running in the final set-up.
Service and Repair
Installation Guide | VLT® Safety Option MCB 150/151
AQ279747441421en-000101 / 130R0292