EasyManuals Logo

Danfoss VLT series Installation Guide

Danfoss VLT series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
3.6.3 Attaching the Unit to the Pedestal
CAUTION
IMPROPER ALIGNMENT
Improper alignment and insucient installation, can
cause damage to the unit and injury.
Only qualied and authorised personnel shall do this
installation.
NOTICE
Illustration 3.12 shows an example. The procedure to be
applied depends on the surface the unit is mounted to,
and is therefore application-specic. The procedure
described here shows the general principle.
1. Lift the unit and position it on the pedestal. Refer
to chapter 3.5.3 Lifting the Unit.
2. Verify that there is 225 mm (9 in) top clearance
for air exhaust.
3. Verify that the air intake from the bottom of the
unit is not obstructed.
4. Make sure that the unit is aligned to the surface
and the surrounding units. Refer to
Illustration 3.11.
5. Install each M8x60 mm bolt with lock washer and
at washer through the frame into the threaded
hole in the base. Install 4 bolts per cabinet. Refer
to Illustration 3.12.
6. Install each M10x30 mm bolt with captive lock
washer and at washer through the base plate
and into the threaded hole in the base. Install 4
bolts per cabinet. Illustration 3.12.
130BE494.10
Illustration 3.11 Unit Alignment
Mechanical Installation
VLT
®
Plus Panel
20 Danfoss A/S © 09/2015 All rights reserved. MG13B102
33

Other manuals for Danfoss VLT series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT series and is the answer not in the manual?

Danfoss VLT series Specifications

General IconGeneral
SeriesVLT
CategoryDC Drives
Output Voltage0-100% of input voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short Circuit, Ground Fault
Communication InterfacesProfibus, CANopen
Enclosure RatingIP20, IP21, IP55, IP66
Cooling MethodForced Air Cooling, Convection Cooling
Control ModeSensorless Vector, Closed Loop Vector
Ambient Temperature-10°C to +50°C (14°F to 122°F)

Related product manuals