5 Specications
5.1 Technical Design Considerations
WARNING
FUNCTIONAL-SAFETY COMPLIANT USE
The VLT
®
Plus Panel is a product in accordance with the
Low Voltage Directive 2006/95/EG, but does not provide
safety-related control functionality in accordance with
Machine Safety Directive 2006/42/EG. CE declaration is
therefore related to EMC (2004/108/EG) and LV Directive.
Failure to take the necessary safety-related control
measures can result in death or serious injury.
•
The panel operator has to ensure the proper
use of the product, even when Safe Torque O
(STO) functionality is used, for example for
ATEX-conform motor thermal protection. In this
case, the safety function is part of the approved
motor thermal protection, using the function as
appropriate energy cut-o.
•
Any other use of the safety functions is in sole
responsibility of the end user, including certi-
cation, documentation, and so on.
•
Customized variants can dier and are not
subject to the panel congurator product
description.
NOTICE
The notication of maximum possible cross-section and
number of wires is shown in drawings for each main
component, where mains and motor cables can be
directly connected. The drawings are provided with the
panel.
Electrical specications
Mains supply 400 V, 500 V, or 690 V, PEN, 3-phase, 50 Hz, IT or
TN, as selected.
Maximum
short circuit
capabilities
I
CW
= 35 kA on infeed terminals of the panel, see
Table 5.2.
Assembly
rated current
I
nA
In accordance with the relevant frequency
converter current rating.
NOTICE
For VLT
®
AutomationDrive FC 302, NO
(normal overload) values are used for the
design. Due to the 80% design rule of EN
61439-2, design is adjusted for the HO
(high overload) use. Details are provided
per power rating in the relevant
documents.
RDF RDF is specied to 1 for all power circuitry as
only 1 frequency converter is foreseen per panel/
infeed.
Cables/wires Cables/wires used according to DIN standards,
cross-section in mm
2
. Any specied power cable
can be used. Always consider local standards
must always be taken into considerations.
Energy
cabling
Energy cabling is done directly to the relevant
terminals of switchgear, frequency converter, or
lter.
Cable entry Bottom cable entry.
Wiring color
code
According to DIN EN 60204-1.
Table 5.1 Electrical Specications
Power
[kW]
Fuse
1)
I
CW
(200 ms) I
C
Let through energy
(200 ms)
I
CC
for I
CW
@35
kA
I
2
t@35 kA PE [mm
2
]
90 kW 3NA7 140 2.2 kA 5.6 kA
945 kA
2
s
15 kA
400 kA
2
s
30x5
110 kW 3NA7 144 2.9 kA 7.4 kA
1673 kA
2
s
19.3 kA
780 kA
2
s
30x5
132 kW 3NA7 252 4 kA 10.2 kA
3238 kA
2
s
24.1 kA
1275 kA
2
s
30x10
160 kW 3NA7 260 5.1 kA 12.9 kA
5508 kA
2
s
29.5 kA
2150 kA
2
s
30x10
200 kW 3NA3 365 7.7 kA 19.5 kA
11409 kA
2
s
39.3 kA
2700 kA
2
s
30x10
250 kW 3NA3 365 7.7 kA 19.5 kA
11409 kA
2
s
39.3 kA
2700 kA
2
s
30x10
315 kW 3NA3 372 10.5 kA 26.8 kA
21848 kA
2
s
48.7 kA
5400 kA
2
s
30x10
Table 5.2 Short Circuit Withstand Capability According to DIN EN 61439
1) Siemens example; fuses with same characteristics from other suppliers can be used.
Specications Installation Guide
MG13B102 Danfoss A/S © 09/2015 All rights reserved. 29
5 5