2.3.1 Before Commencing Repair Work
1.
Disconnect the VLT
®
Plus Panel from mains.
2. Disconnect DC bus terminals 88 and 89 from load
share applications.
3. Wait for discharge of the DC-link, see Table 2.1.
The discharge time is also printed on the warning
label.
4. Remove motor cable.
Safety
VLT
®
Plus Panel
10 Danfoss A/S © 09/2015 All rights reserved. MG13B102