EasyManuals Logo

Danfoss VLT series Installation Guide

Danfoss VLT series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
4.4 Fuses
4.4.1 Motor Insulation
For motor cable lengths the maximum cable length
listed in chapter 5
Specications, the recommended motor
insulation ratings are in Table 4.1. The peak voltage can be
up to twice the DC-link voltage, 2.8 times the mains
voltage, due to transmission line eects in the motor cable.
If a motor has a lower insulation rating, use a dU/dt or sine
wave lter.
Nominal mains voltage Motor insulation
U
N
420 V
Standard U
LL
= 1300 V
420 V <U
N
≤500 V Reinforced U
LL
= 1600 V
500 V <U
N
≤600 V Reinforced U
LL
= 1800 V
600 V <U
N
≤690 V Reinforced U
LL
= 2000 V
Table 4.1 Motor Insulation at Various Nominal Mains Voltages
4.4.2 Motor Bearing Currents
All motors installed with FC 302 90 kW or higher power
frequency converters should have NDE (non-drive end)
insulated bearings installed to eliminate circulating bearing
currents. To minimize DE (drive end) bearing and shaft
currents, proper grounding of the frequency converter,
motor, driven machine, and motor to the driven machine is
required.
Standard mitigation strategies:
1. Use an insulated bearing.
2. Apply rigorous installation procedures.
2a Ensure that the motor and load motor
are aligned.
2b Strictly follow the EMC installation
guideline.
2c Reinforce the PE so the high frequency
impedance is lower in the PE than the
input power leads.
2d Provide a good high frequency
connection between the motor and the
frequency converter. Achieve that for
example by using a screened cable
which has a 360° connection in the
motor and the frequency converter.
2e Make sure that the impedance from
frequency converter to building ground
is lower than the grounding impedance
of the machine. This can be dicult for
pumps.
2f Make a direct ground connection
between the motor and load motor.
3. Lower the IGBT switching frequency.
4.
Modify the inverter waveform, 60° AVM versus
SFAVM.
5. Install a shaft grounding system or use an
isolating coupling.
6. Apply conductive lubrication.
7. Use minimum speed settings if possible.
8. Try to ensure that the line voltage is balanced to
ground. This can be dicult for IT, TT, TN-CS or
grounded leg systems.
9. Use a dU/dt or sinus lter.
4.4.3 Control Cable Routing
Tie down all control wires to the designated control cable
routing. To ensure optimum electrical immunity, connect
the screens properly.
Fieldbus connection
Connections are made to the relevant options on the
control card. For details, see the relevant eldbus
instruction. Place the cable in the provided path inside the
frequency converter and tie it down with other control
wires.
Electrical Installation
VLT
®
Plus Panel
28 Danfoss A/S © 09/2015 All rights reserved. MG13B102
44

Other manuals for Danfoss VLT series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT series and is the answer not in the manual?

Danfoss VLT series Specifications

General IconGeneral
SeriesVLT
CategoryDC Drives
Output Voltage0-100% of input voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short Circuit, Ground Fault
Communication InterfacesProfibus, CANopen
Enclosure RatingIP20, IP21, IP55, IP66
Cooling MethodForced Air Cooling, Convection Cooling
Control ModeSensorless Vector, Closed Loop Vector
Ambient Temperature-10°C to +50°C (14°F to 122°F)

Related product manuals