4.1.1 Initial Commissioning
The easiest way of carrying out the initial commissioning is by pressing [Quick Menu] and following the quick set-up
procedure using LCP 102 (read Table 4.1 from left to right). The example applies to open-loop applications.
Press
Quick
Menu
Q2 Quick Menu.
OK
Parameter 0-01 LanguageParameter 0-
01 Language
OK
Set language.
Parameter 1-20 Motor Power [kW]
OK
Set motor nameplate power.
Parameter 1-22 Motor Voltage
OK
Set nameplate voltage.
Parameter 1-23 Motor Frequency
OK
Set nameplate frequency.
Parameter 1-24 Motor Current
OK
Set nameplate current.
Parameter 1-25 Motor Nominal Speed
OK
Set nameplate speed in RPM.
Parameter 5-12 Terminal 27 Digital
Input
OK
If terminal default is [2] Coast
inverse, it is possible to change
this setting to [0] No function.
No connection to terminal 27 is
then needed for running AMA.
Parameter 1-29 Automatic Motor
Adaptation (AMA)
OK
Set desired AMA function.
Enable complete AMA is
recommended.
Parameter 3-02 Minimum Reference
OK
Set the minimum speed of the
motor shaft.
Parameter 3-03 Maximum Reference
OK
Set the maximum speed of the
motor shaft.
Parameter 3-41 Ramp 1 Ramp Up Time
OK
Set the ramp-up time with
reference to synchronous motor
speed, n
s
.
Parameter 3-42 Ramp 1 Ramp Down
Time
OK
Set the ramp-down time with
reference to synchronous motor
speed, n
s
.
Parameter 3-13 Reference Site
OK
Set the site from where the
reference must work.
Table 4.1 Quick Set-up Procedure
How to Programme Operating Instructions
MG34Q402 Danfoss A/S © 04/2016 All rights reserved. 61
4 4

Table of Contents

Other manuals for Danfoss VLT series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT series and is the answer not in the manual?

Danfoss VLT series Specifications

General IconGeneral
SeriesVLT
CategoryDC Drives
Output Voltage0-100% of input voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short Circuit, Ground Fault
Communication InterfacesProfibus, CANopen
Enclosure RatingIP20, IP21, IP55, IP66
Cooling MethodForced Air Cooling, Convection Cooling
Control ModeSensorless Vector, Closed Loop Vector
Ambient Temperature-10°C to +50°C (14°F to 122°F)