35•dap4UserManual
PresstheDOWNkeytoviewthenextscreen:
The following will be displayed (inputs are for reference only):
Available Selections:
One, two, three, 1-Elect, 3-Elect, or none
If two or three are selected, the display module will display “Lead Reheat:”
By pressing the UP or DOWN key the lead choices (First, Second or Third) can be seen.
With two stage reheat, pick either First or Second (factory setting is First)
With three stage reheat, pick either First, Second or Third (factory setting is First)
Once a selection or selections have been made, move the cursor to the title block by pressing the
ENTER key
▼PresstheDOWNkeytoviewthenextscreen:
The following will be displayed (inputs are for reference only):
Reheat Settings
Reheat Stages: 3-Elect
Lead Reheat: First
Enable SCR Y4: Yes
Band: 1°F
Reheat Settings
Reheat Stages: Three
Lead Reheat:
Water Valve Settings
Wtr Vlv: Engy Svg Cool
E-Saver Assist: None
Wtr Vlv Voltage: 0-10
Wtr Vlv Action: Direct
Engy Lockout Time: 15m