This parameter controls e-mail sending
when IP address of GPRS or ethernet
connection is changed. No warnings
generated.
0: no e-mail on IP change
1: e-mail sent on IP change
If the fuel level measured from the
sender input falls below this level, then
the FUEL PUMP function will become
active.
If the fuel level measured from the
sender input goes above this level, then
the FUEL PUMP function will become
passive.
This parameter controls the activation of
the ALARM output during “Engine Start
Delay” timer before engine run.
0: no warning before start
1: warning before start
0: warnings are latching/non-latching on
parameter control
1: all warnings are latched. Even if the
fault source is removed, warnings will
persist until manually reset.
This parameter controls remote control
of the unit through Rainbow, Modbus
and Modbus TCP/IP.
0: remote control disabled
1: remote control enabled
0: normal operation
1: the unit becomes an annunciator of
the remote unit. Engine/genset control
functions are disabled.
0: CTs are at the genset side. Mains
currents are not measured.
1: CTs are at load side. Both mains and
genset currents are monitored following
contactor status.
This parameter is useful to invert all CT
polarities at the same time.
0: normal CT polarity assumed.
1: reverse CT polarity assumed.
Internal buzzer control
0: buzzer disabled
1: buzzer enabled
This parameter adjusts the data logging
frequency to micro-SD or USB Flash
memories. Frequent recording will
require more memory capacity.
With a period of 2 seconds, 4GB per
year of memory is necessary.
With a period of 1 minute, 133MB is
consumed per year.
17.1. CONTROLLER CONFIGURATION GROUP (continued)