D-500 MK2 User Manual Firmware V-6.3
- 103 -
This is the number of pulses produced
by the flowmeter for the unit volume.
This parameter is characteristic of the
flowmeter used and should be set
according to the flowmeter data.
This is the unit for the fuel counter
This parameter controls SMS sending
when the engine runs or stops. No
warnings generated.
0: no SMS on engine run/stop
1: SMS sent on engine run/stop
E-mail on Engine
Run/Stop
This parameter controls e-mail sending
when the engine runs or stops. No
warnings generated.
0: no e-mail on engine run/stop
1: e-mail sent on engine run/stop
This parameter determines the purpose
of fuel pulses
0: Fuel filling pulses, increment fuel
counter
1: Fuel consumption pulses, display
consumption.
Dual Genset Equal Aging
Enabled
0: Equal aging not enabled
1: Equal aging enabled
Automatic Topology
Detection
If this parameter is enabled, when the
engine runs, the controller will detect
the connection topology automatically
and will select alarm levels accordingly.
0: auto detect not enabled
1: auto detect enabled
Maintenance Done
Warning Enable
If enabled, the unit will generate a non-
visual warning when maintenance
counters are reset. In consequence,
SMS and e-mails will be sent, the
warning will be visible on the central
monitoring system.
0: maintenance warning disabled
1: maintenance warning enabled
0: Enable status screens
1: Disable status screens
This parameter adjusts the time zone of
the controller, in order to allow internal
real time clock to be synchronized to
the UTC time.
0: no location information from GSM
1: location information read from GSM
system.
0: When Loaddump alarm occurs,
genset contactor opens and genset
runs until the end of the cooldown
1: When Loaddump alarm occurs,
genset contactor opens but the genset
continues running without timeout.
17.1. CONTROLLER CONFIGURATION GROUP (continued)